(4) Display of Outdoor Cycle Data (Displayed at Header Unit)
* This method is used when displaying follower unit information on the 7-segment display of the header unit.
63
7-Segment Display Function (Continued)
SW01
SW02
SW03
Display detail
1
A
Error data
[U.2]
B Check code is displayed (latest one only).
If there is no check code: [– – –].
Unused
2
5
3
1
A
Fan operation mode
[U.2]
B At rest: [F ... 0], In mode 63: [F 6 3]
6
A
Release signal
[U.2]
B Normal: [r ... ...], Upon receiving release signal: [r ... 1]
7
A
Oil level judgment
[U.2]
B Normal: [... ... ...], Low level: [... ... L]
8
A
Compressor 1 operating current
[U.2]
B [
∗∗
.
∗
],
∗∗
.
∗
is value of operating current in decimal format.
9
A
Compressor 2 operating current
[U.2]
B [
∗∗
.
∗
],
∗∗
.
∗
is value of operating current in decimal format.
10
A
Compressor 3 operating current
[U.2]
B [
∗∗
.
∗
],
∗∗
.
∗
is value of operating current in decimal format.
11
A
Fan operating current
[U.2]
B [
∗∗
.
∗
],
∗∗
.
∗
is value of operating current in decimal format.
4
A
Compressor operation command
[U.2]
B Indicates which compressor is ON.
When compressor No. 1 is ON
When compressor No. 2 is ON
When compressor No. 3 is ON
∗
Any unconnected compressors is represented by “–”
1 0 0
0 1 0
0 0 1
A