31
Cooling / heating test operation check
The cooling/heating test operation check can be performed on both the indoor remote control and the outdoor
header unit interface PC board.
(1) Test operation start/stop operation
Test operation from the indoor remote control
• Wired remote control: Refer to the items below in “Test operation” of the wired remote control.
• Wireless remote control: Refer to the items below in “Test operation” of the wireless remote control.
Wired remote control
Wireless remote control (Except the 4-way
Cassette type and the Ceiling type)
1, 5
3
2, 4
Operation content
Procedure
1
2
When the Test button is pushed for 4 seconds or
more, “TEST” is displayed in the display section,
and the unit enters test operating mode.
5
Push the Test button to clear the test operating mode.
(“TEST” disappears from the display section, and
the status returns to the normal stopped status.)
3
Using the Select Mode button, select the
“ COOL” or “ HEAT” operating mode.
• Do not use an operating mode other than
“ COOL” or “ HEAT”.
• Temperature adjustment is unavailable during
test operation.
• Error is detected as usual.
Push the button.
4
When the test operation has finished, push the
button to stop the operation.
(The same display as in procedure 1 appears in
the display section.)
Operation content
Procedure
1
2
Remove the nameplate of the receiver section by
inserting a screwdriver or similar tool into the
notch at the bottom of the plate, and set the DIP
switch to “TEST RUN ON.”
4
3
Use either the “ COOL” or “ HEAT”
operation mode for a test operation.
* The outdoor unit does not operate for
approximately 3 minutes after powering-on or
stopping operation.
Execute a test operation with the button on the
wireless remote control.
• The “ ”, “ ” and “ ” LEDs blink during test
operation.
• Under “TEST RUN ON” status, temperature
adjustment from the wireless remote controller
is invalid.
Do not use this method of operation other than for
test operation because the equipment will be
damaged.
After the test operation is finished, stop the air
conditioner from the wireless remote controller,
and return the DIP switch of the sensor section to
its original position.
(A 60-minute timer clearing function is attached to
the sensor section in order to prevent continuous
test operation.)
M4 × 25 screw
(2 pieces)
Receiver unit
Spacer
Nameplate
Notch
Small screw
Test Operation Setup (Remote Conntroller)