37
In checking the number of connected outdoor units and connected indoor
units after address setup, a lower number of connected units is displayed.
(There are outdoor/indoor units that do not operate in a test operation.)
Status
Cause
Countermeasures
The number of
connected
outdoor units is
too few.
Miswiring of communication lines between outdoor units
or an unconnected wire. (Address setup operation
finished without recognizing a miswired follower unit.)
After modification of wiring, set up the addresses again and
check the number of connected outdoor units.
The number of
connected indoor
units is too few.
Miswiring of communication lines between indoor units
or an unconnected wire. (Address setup operation
finished without recognizing a miswired indoor unit.)
After modification of wiring, set up the addresses again and
check the number of connected indoor units.
The number of
outdoor units
connected to a
group is too few in
group operation
from an indoor
remote controller.
The indoor remote controller is not connected with wire.
Miswiring of the indoor remote controller
Using the main indoor remote controller connected to a group,
start a test operation, specify the unit that is not operating (the
unit not connected to the group), and then check the wiring.
Indoor remote controller communication circuit error
If 208/230V or 460V is ctly applied to the remote controller
terminal, the remote controller communication circuit fails.
Using the main indoor remote controller connected to a group,
start a test operation and then specify the unit that is not
operating (the unit not connected to the group). Remove the
fast-on terminal connected to remote controller terminals A/B,
and check the voltage. If voltage is not applied (normally 15
to18 V), replace the PC board.
Troubleshooting in Test Operation (Continued)