F-GAS label
This product contains
fl
uorinated greenhouse gases covered by the Kyoto Protocol
• Chemical Name of Gas
R410A
• Global Warming Potential (GWP) of Gas
1975
CAUTION
1. Stick the enclosed refrigerant label adjacent to the charging and/or recovering location.
2. Clearly write the charged refrigerant quantity on the refrigerant label using indelible ink. Then, place the
included transparent protective sheet over the label to prevent the writing from rubbing off.
3. Prevent emission of the contained
fl
uorinated greenhouse gas. Ensure that the
fl
uorinated greenhouse gas is
never vented to the atmosphere during installation, service or disposal. When any leakage of the contained
fl
uorinated greenhouse gas is detected, the leak shall be stopped and repaired as soon as possible.
4. Only quali
fi
ed service personnel are allowed to access and service this product.
5. Any handling of the
fl
uorinated greenhouse gas in this product, such as when moving the product or recharging
the gas, shall comply under (EC) Regulation No. 842/2006 on certain
fl
uorinated greenhouse gases and any
relevant local legislation.
6. Periodical inspections for refrigerant leaks may be required depending on European or local legislation.
7. Contact dealers, installers, etc., for any questions.
R410A
kg
kg
kg
Pre-charged Refrigerant at Factory [kg],
speci
fi
ed in the nameplate
Additional Charge on Installation Site
[kg]
Full opening of the valve
Open the valves of the outdoor unit fully.
MAP080
MAP100
MAP120
MAP140
MAP160
MAP180
MAP200
Balance pipe
Packed valve
Using a 4 mm-hexagonal wrench, fully open the valve shaft.
Liquid side
Ø12.7 packed valve
Using a 4 mm-hexagonal wrench, fully open the
valve shaft.
Ø15.9 packed valve
Using a 5 mm-hexagonal wrench, fully open the
valve shaft.
Discharge gas
side
Ball valve
Using a
fl
athead screwdriver, turn it counterclockwise by 90° until it hits the stopper. (Full open)
(1)
(2)
Service port
Valve unit
Using
fl
athead screwdriver, turn
it counterclockwise by 90° until
it hits the stopper. (Full open)
Flare nut
Position of screwdriver slot
Fully closed
Fully opened
Slot
* When opened fully, do not apply excessive
torque after the screwdriver hits the
stopper; otherwise a problem may be
caused on the valve. (5 N•m or less)
Suction gas side
Ball valve
Using a wrench, turn the valve shaft counterclockwise by 90° until it hits the stopper. (Full open)
Fully closed
Fully opened