127
(*1) All stop only in case of the header unit The follower unit continues operation.
MG-SW : Magnet Switch, OCR : Over-current Relay
Check code
Outdoor 7-segment display
Main
remote
controller Check code
Sub-code
AI-NET
central control
remote controller
Detected
position
Check code name
Status
Error detection condition
Check item (position)
F13
F13
01: Compressor 1 side
02: Compressor 2 side
43
IPDU
TH sensor error
All stop
• Resistance value of sensor is
infinite or zero (Open/Short).
• IGBT built-in temp sensor error
→
Exchange IPDU P.C. board.
F15
F15
—
18
I/F
Outdoor temp sensor
miscabling (TE1, TL)
All stop
During operation of
compressor in HEAT mode, the
TE1 detection temp was higher
than that of TL by the specified
value continued for 3 minutes
or more.
• Check installation of TE1 sensor and TL sensor.
• Check characteristics of TE1 and TL sensor resistance value.
• Check outdoor P.C. board (I/F) error.
F16
F16
—
43
I/F
Outdoor pressure
sensor miscabling
(Pd, Ps)
All stop
High-pressure Pd sensor and
low-pressure Ps sensor were
exchanged, or output voltages
of both sensors are zero.
• Check connection of high-pressure Pd sensor connector.
• Check connection of low-pressure Ps sensor connector.
• Check pressure sensors Pd and Ps error.
• Check outdoor P.C. board (I/F) error.
• Check compression error of compressor.
F23
F23
—
43
I/F
Ps sensor error
All stop
Output voltage of Ps sensor
was zero.
• Misconnection of Ps sensor and Pd sensor connectors
• Check connection of Ps sensor connector.
• Check Ps sensor error.
• Check compression error of compressor.
• Check 4-way valve error.
• Check outdoor P.C. board (I/F) error.
• Check SV4 circuit error.
F24
F24
—
43
I/F
Pd sensor error
All stop
Output voltage of Pd sensor
was zero. (Sensor Open)
Pd > 4.15MPa during stop of
compressor
• Check connection of Pd sensor connector.
• Check Pd sensor error.
• Check outdoor P.C. board (I/F) error.
F29
—
—
12
Indoor
Indoor other error
Corresponding
unit only stops.
Indoor P.C. board did not
operate normally.
• Check indoor P.C. board error (EEPROM error).
F31
F31
—
1C
I/F
Outdoor EEPROM error
All stop (*1)
Outdoor P.C. board (I/F) did not
operate normally.
• Check power voltage.
• Check power noise.
• Check outdoor P.C. board (I/F) error.
H01
H01
01: Compressor 1 side
02: Compressor 2 side
1F
IPDU
Compressor breakdown
All stop
Inverter current detection circuit
detected over-current and
stopped.
• Check power voltage. (AC220–240V ± 10%).
• Check compressor error.
• Check cause of abnormal overload operation.
• Check outdoor P.C. board (IPDU) error.
H02
H02
01: Compressor 1 side
02: Compressor 2 side
1d
IPDU
Compressor error (lock)
MG-SW error
OCR operation
All stop
Over-current was detected
several seconds after header
compressor had started.
• Check compressor error.
• Check power voltage. (AC380–10%, 415V +10%).
• Check cable of compressor and phase-missing.
• Check connector/terminal connection on IPDU P.C. board.
• Check conduction of case heater.
(Check activation error due to liquid stagnation in compressor.)
• Check outdoor P.C. board (IPDU) error.
• Check outdoor MG-SW or OCR.