143
Auxiliary code
01
02
03
04
05
06
07
P.C. board to be replaced
IPDU1
IPDU2
IPDU1, 2
Fan IPDU
IPDU1, fan IPDU
IPDU2, fan IPDU
IPDU1, 2, fan IPDU, I/F
Is jumper lead setup on the outdoor I/F P.C. board correct?
(Jumper 7, 8, 9 ON)
NO
NO
YES
YES
YES
YES
YES
NO
NO
NO
NO
YES
Connect the jumper lead.
Correct connection.
Connect the communication line.
I/F P.C. board error
IPDU P.C. board error
Replace fan power P.C. board.
Are communication connectors
between I/F fan power P.C. board,
and IPDU connected?
Is there voltage between pin 4 and
pin 5 of CN600 on I/F P.C. board?
(Measure with tester: DC0 to 5 V)
Is there voltage deflection between
pin 3 and pin 5 of CN600 on I/F P.C. board?
(Measure with tester: DC 0 to 5V, 5 pin GND)
On the fan power supply P.C. board,
1) CN503: Between pins 1 and 5
®
12V
2) CN503: Between pins 2 and 5
®
7V
3) Between +5V and GND of CN505: 5V
Replace P.C. board according to auxiliary code.
Is there disconnection on communication line
between IPDU and I/F P.C. board?
Check code
[E31] / [CF]
(TCC-L / AI-NET)
Check code name
IPDU communication error
Cause of operation
1. Connection error of communication line
between IPDU and I/F P.C. board
2. I/F P.C. board error
3. IPDU P.C. board error
4. External noise
Sub-code:
01: IPDU1 error
02: IPDU2 error
03: IPDU1, 2 error
04: Fan IPDU error
05: IPDU1, fan IPDU error
06: IPDU2, fan IPDU error
07: All IPDU error or communication line error between IPDU-I/F P.C. boards, or outdoor I/F P.C. board error
∗
If the fan IPDU is abnormal, be sure to check the voltage output on the fan power P.C. board.
Check code
[F01] / [0F]
(TCC-L / AI-NET)
Check code name
Indoor TCJ sensor error
Cause of operation
TCJ sensor Open/Short
YES
YES
NO
NO
Correct connection.
Replace TC1 sensor.
Is TC1 sensor connector (CN100: Brown)
on indoor P.C. board normally connected?
Are characteristics of TC1 sensor
resistance value normal?
*
Check indoor main P.C. board.
Defect
®
Replace
*
Indoor unit temperature sensor characteristics
See Characteristics-2.
Check code
[F03] / [93]
(TCC-L / AI-NET)
Check code name
Indoor TC1 sensor error
Cause of operation
TC1 sensor Open/Short
Check code
[F02] / [0d]
(TCC-L / AI-NET)
Check code name
Indoor TC2 sensor error
Cause of operation
TC2 sensor Open/Short
YES
YES
NO
NO
Correct connection.
Replace TCJ sensor.
Is TCJ sensor connector (CN102: Red)
on indoor P.C. board normally connected?
Are characteristics of TCJ sensor
resistance value normal?
∗
Check indoor main P.C. board.
Defect
®
Replace
*
Indoor unit temperature sensor characteristics
See Characteristics-2.
Correct connection.
Replace TC2 sensor.
Is TC2 sensor connector (CN101: Black)
on indoor P.C. board normally connected?
Are characteristics of TC2 sensor
resistance value normal?
*
Check indoor main P.C. board.
Defect
®
Replace
YES
YES
NO
NO
*
Indoor unit temperature sensor characteristics
See Characteristics-2.