– 42 –
How to change all indoor addresses from an arbitrary wired remote control
(It is possible when setting has finished by automatic addresses.)
Contents:
The indoor unit addresses in each identical refrigerant piping line can be changed from an
arbitrary wired remote control.
Enter in address check/change mode and then change the address.
<Procedure>
Carry out this procedure during stop of system.
1
Push the timer time button
+ simultaneously for 4 seconds or more.
First line 1 and CODE No.
AC
AC
AC
AC
AC
(Address Change) are displayed.
Ø
2
Select line address using
UNIT LOUVER
/
SWING/FIX
button.
Ø
3
Push the button.
• The address of the indoor unit connected to the
refrigerant piping of the selected outdoor unit is
displayed and the fan is on.
First the current indoor address is displayed.
(Line address is not displayed.)
Ø
4
button push up/down the indoor
address of the SET DATA.
The set data is changed to a new address.
Ø
5
Push button to determine the set data.
Ø
6
Every pushing
UNIT LOUVER
button (button at left
side), the indoor unit No. in the identical
piping is displayed one after the other.
• Only fan of the selected indoor unit start
operation.
Repeat the Procedures
4
to
6
to change all the
indoor addresses so that they are not duplicated.
Ø
7
Push button.
(All the indications of LCD go on.)
Ø
8
Push button and then the procedure
finishes.
3
1
2
SET
TIME
TIMER SET
TEST
FILTER
RESET
CL
FAN
SAVE
SWING/FIX
VENT
MODE
ON / OFF
UNIT LOUVER
1 2 3 4 5
6 7 8
END
<Operation procedure>
5
4
6
7
SET
TIME
TIMER SET
TEST
FILTER
RESET
CL
FAN
SAVE
SWING/FIX
VENT
MODE
ON / OFF
UNIT LOUVER
Cancel of line selection
When you want to
complete the setting
8
Finish
TEMP.
TEMP.
If the UNIT No. is not called up here, the outdoor unit
in that line does not exist.
Push
CL
button to select a line again in the
Procedure
2
.