No.
5
Item
Fan speed
selection
(Continued)
Outline of specifications
<HEAT>
Remarks
Value in the parentheses indicates one when thermostat of
the remote control works.
Value without parentheses indicates one when thermostat of
the Indoor unit works.
• If the fan speed has been changed once, it is not changed
for 1 minute. However when the air volume changes, the
fan speed changes.
• When heating operation has started, select an upward
slope for the fan speed, that is, the high position.
• If the temperature is just on the margin the fan speed does
not change.
• In TC2
≥
140°F[60°C], the fan speed increases by clarify 1
step.
TC2: Indoor heat
exchanger sensor
temperature
6
Prevention of
cold air
discharge
1. In heating operation, the higher temperature of TC2 sensor
and TCJ sensor is compared with temperature of TC1
sensor and then the lower temperature is used to set the
upper limit of the fan tap.
• When B zone has continued for 6 minutes, the opera-
tion shifts to C zone.
• In defrost time, the control point is set to +10.8°F[6°C].
TCJ: Temperature of
indoor heat
exchanger sensor
TC1: Temperature of
indoor heat
exchanger sensor
• In D and E zones,
priority is given to
remote control air
speed setup.
• In A zone “
” is dis-
played.
TA ˚F (˚C)
(– 0.9) – 1.8 [(– 0.5) – 1.0]
(0) Tsh
(+0.9) +1.8 [(+0.5) +1.0]
(+1.8) +3.6 [(+1.0) +2.0]
(+2.7) +5.4 [(+1.5) +3.0]
(+3.6) +7.2 [(+2.0) +4.0]
L <L>
L <H>
H <H>
HH
<HH>
H
<HH>
E
D
C
B
A
Indoor unit thermostat works.
Remote control thermostat works.
< > : Indicate automatic heating.
E
B
A
A zone: OFF
B zone:
Over 72°F (26°C), below 82°F (28°C), ULTRA LOW (LL)
C zone:
Over 82°F (28°C), below 86°F (30°C), LOW (L)
D zone:
Over 86°F (30°C), below 90°F (32°C), MED (H)
E zone: HIGH (HH)
D
C
90 (32)
86 (30)
82 (28)
75 (26)
68 (20)
61 (16)
°F (°C)