<RBC-ASCU11-
>
Be sure to stop the air conditioner before making settings.
(Change the setup while the air conditioner is not working.)
1
Push and hold OFF timer button and [
] setting button simultaneously for 10 seconds or
more. [TEST] is displayed on the display part and the test run is permitted.
2
Push ON/OFF button.
3
Push menu button to select the operation mode. Select [
Cool] or [
Heat] with [
]
[
] setting button.
• Do not run the air conditioner in a mode other than [Cool] or [Heat].
• The temperature setting function does not work during test run.
• The check code is displayed as usual.
4
After the test run, push OFF timer button to stop a test run.
([TEST] disappears on the display and the air conditioner enters the normal stop mode.)