5
Push the menu button to make Set data
[
]
fl
ash. Change Set data [
]
with [ ] [ ] setting button.
6
Push OFF timer button.
By doing so, the setup is completed.
•
To change other settings of the selected
indoor unit, repeat from Procedure
4
.
7
When all the settings have been
completed, push ON/OFF button to
determine the settings.
“
”
fl
ashes and then the display content
disappears and the air conditioner enters the
normal stop mode. (The remote controller is
unavailable while “
” is
fl
ashing.)
• To change settings of another indoor unit,
repeat from Procedure
1
.
Change of lighting time of
fi
lter
sign
According to the installation condition, the lighting
time of the
fi
lter sign (Noti
fi
cation of
fi
lter cleaning)
can be changed.
Follow to the basic operation procedure
(
1
→
2
→
3
→
4
→
5
→
6
).
• For the CODE No. in Procedure
4
, specify [01].
• For the [SET DATA] in Procedure
5
, select the
SET DATA of
fi
lter sign lighting time from the
following table.
SET DATA
Filter sign lighting time
0000
None
0001
150H (Factory setting)
0002
2500H
0003
5000H
0004
10000H
To secure better effect of heating
When it is dif
fi
cult to obtain satisfactory heating
due to installation place of the indoor unit or
structure of the room, the detection temperature of
heating can be raised. Also use a circulator, etc.
to circulate heat air near the ceiling.
Follow to the basic operation procedure
(
1
→
2
→
3
→
4
→
5
→
6
).
• For the CODE No. in Procedure
4
, specify [06].
• For the SET DATA in Procedure
5
, select
the SET DATA of shift value of detection
temperature to be set up from the table below.
SET DATA
Detection temp shift value
0000
No shift
0001
+1°C
0002
+2°C (Factory setting)
0003
+3°C
0004
+4°C
0005
+5°C
0006
+6°C
BOOK_1130550101_EN.indd 34
BOOK_1130550101_EN.indd 34
11/2/2564 BE 19:18
11/2/2564 BE 19:18
- 119 -