Electrical connection

WARNING

Use the specified wires for wiring connect the 
terminals. Securely fix them to prevent external 
forces applied to the terminals from affecting the 
terminals.

Incomplete connection or fixation may cause a fire or 
other trouble.

Connect earth wire. (grounding work)

Incomplete grounding cause an electric shock.
Do not connect earth wires to gas pipes, water pipes, 
lightning conductor or telephone earth wires.

Appliance shall be installed in accordance with 
national wiring regulations.

Capacity shortage of power circuit or incomplete 
installation may cause an electric shock or a fire.

CAUTION

• If incorrect / incomplete wiring is carried out, it will 

cause an electrical fire or smoke.

• Use the cord clamps attached to the product.
• Do not damage or scratch the conductive core and 

inner insulator of power and inter-connecting wires 
when peeling them.

• Use the power cord and Inter-connecting wire of 

specified thickness, type, and protective devices 
required.

• Do not connect 220 V – 240 V power to the terminal 

blocks (

) for control wiring. (Otherwise, 

the system will fail.)

• Do not allow the electric wiring to touch the hot pipes. 

Doing so could melt the coatings.

REQUIREMENT

• For power supply wiring, strictly conform to the Local 

Regulation in each country.

• For wiring of power supply of the outdoor units, follow 

the Installation Manual of each outdoor unit.

• After connecting wires to the terminal blocks, provide 

a trap and fix wires with the cord clamp.

• Run the refrigerant piping line and control wiring line in 

the same line.

• Do not turn on the power of the indoor unit until the 

refrigerant pipes are vacuumed.

Power supply wire and 
communication wires 
specifications

Power supply wire and communication wires are 
procured locally.
For the power supply specifications, follow to the 
following table. If capacity is little, it is dangerous 
because overheat or burnout may be caused.
For specifications of the power capacity of the outdoor 
unit and the power supply wires, refer to the Installation 
Manual attached to the outdoor unit.

Indoor unit power supply

• For the power supply of the indoor unit, prepare the 

exclusive power supply separated from that of the 
outdoor unit.

• Arrange the power supply, circuit breaker, and main 

switch of the indoor unit connected to the same 
outdoor unit so that they are commonly used.

• Power supply wire specification: Cable 3-core 2.5 

mm², 

in conformity with Design 60245 IEC 57

.

U

1

U

2

A

B

Power supply

Control wiring, Central controller wiring

• 2-core with polarity wires are used for the Control wiring between indoor unit and outdoor unit and Central 

controller wiring.

• To prevent noise trouble, use 2-core shield wire.
• The length of the communication line means the total length of the inter-unit wire length between indoor and 

outdoor units added with the central control system wire length.

Communication line

Remote controller wiring

2-core with non-polarity wire is used for wiring of the remote controller wiring and group remote controllers wiring.

CAUTION

The remote controller wire (Communication line) and AC 220 – 240 V wires cannot be side-by-side in 

contact with each other and cannot be run in the same conduits. Doing so may cause trouble on the 

control system due to noise or other factors.

Power supply

220 V – 240 V ~, 50 Hz

220 V ~, 60 Hz

Power supply switch / circuit breaker or power supply wiring / fuse rating for indoor units should be selected by the 

accumulated total current values of the indoor units.

Power supply wiring

Below 50 m

2.5 mm

2

Control wiring between indoor units, and 

outdoor unit (2-core shield wire)

Wire size

(Up to 1000 m) 1.25 mm²

(Up to 2000 m) 2.0 mm²

Central control line wiring (2-core shield 

wire)

Wire size

(Up to 1000 m) 1.25 mm²

(Up to 2000 m) 2.0 mm²

Remote controller wiring, remote controller inter-unit 

wiring

Wire size: 0.5 mm² to 2.0 mm²

Total wire length of remote controller wiring and remote 

controller inter-unit wiring = L + L1 + L2 + … Ln

In case of wired type only

Up to 500 m

In case of wireless type 

included

Up to 400 m

Total wire length of remote controller inter-unit wiring = L1 + L2 + … Ln

Up to 200 m

L1

L

L2

Ln

Indoor unit

Remote controller inter-unit wiring

Indoor unit

Indoor unit

Indoor unit

Remote

controller

(Max. 8 units)

Remote 

controller 

wiring

23-EN

24-EN

Содержание MMF-AP0156H1-E

Страница 1: ...r commercial use MMF AP0366H1 E MMF AP0486H1 E MMF AP0566H1 E Indoor Unit Model name Floor Standing Type MMF AP0156H1 E MMF AP0186H1 E MMF AP0246H1 E MMF AP0276H1 E AIR CONDITIONER MULTI TYPE Installation Manual ...

Страница 2: ...lation Manual attached to the outdoor unit ADOPTION OF NEW REFRIGERANT This Air Conditioner uses R410A an environmentally friendly refrigerant Contents 1 Precautions for safety 3 2 Accessory parts 7 3 Selection of installation place 7 4 Installation 8 5 Drain piping 9 6 Refrigerant piping 11 7 Electrical connection 12 8 Applicable controls 14 9 Test run 15 10 Maintenance 16 11 Troubleshooting 17 1...

Страница 3: ...Qualified service person The qualified service person is a person who installs repairs maintains relocates and removes the air conditioners made by Toshiba Carrier Corporation He or she has been trained to install repair maintain relocate and remove the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has been instructed in such operations by an individual or individ...

Страница 4: ...ion of the product or an injury to your body Before opening the intake grille of the indoor unit or service panel of the outdoor unit set the circuit breaker to the OFF position Failure to set the circuit breaker to the OFF position may result in electric shocks through contact with the interior parts Only a qualified installer 1 or qualified service person 1 is allowed to remove the intake grille...

Страница 5: ...xposed to the wind of air conditioner otherwise it may cause imperfect combustion Installation Install the air conditioner securely in a location where the base can sustain the weight adequately If the strength is not enough the unit may fall down resulting in injury Follow the instructions in the Installation Manual to install the air conditioner Failure to follow these instructions may cause the...

Страница 6: ... Before operating the air conditioner after having completed the work check that the electrical control box cover of the indoor unit and service panel of the outdoor unit are closed and set the circuit breaker to the ON position You may receive an electric shock if the power is turned on without first conducting these checks If there is any kind of trouble such as an error display has appeared sme...

Страница 7: ...dopts the new HFC refrigerant R410A which does not destroy ozone layer The characteristics of R410A refrigerant are easy to absorb water oxidizing membrane or oil and its pressure is approx 1 6 times higher than that of refrigerant R22 Accompanied with the new refrigerant refrigerating oil has also been changed Therefore do not let water dust former refrigerant or refrigerating oil enter the refri...

Страница 8: ...y cause the air conditioner s performance to deteriorate condensation to form the plastic parts to be damaged and other such problems to result Locations near obstructions such as ventilation openings or lighting fixtures where the flow of the blown air will be disrupted a disruption of the air flow may cause the air conditioner s performance to deteriorate or the unit to shut down Locations where...

Страница 9: ...vention of accident of falling because this unit is formed into a thin type If it is not fixed a falling accident may occur After carry in the indoor unit to the specified place fix it to the wall and the floor immediately for safety Installation of indoor unit Fixing to the wall surface Use the attached wall fixing bracket by inverting it at upper side of the unit Fix the indoor unit to the wall ...

Страница 10: ...AP036H to AP056H type 258 52 to 102 Air intake grille Bracket for fixing to floor Bracket for fixing to wall Electrical control box cover Vertical louver Turn the vertical louver while lifting up lightly and then insert it into the clearance of extrusion of the coupling rod Extrusion Coupling rod 8 m o r l e s s 5 Drain piping CAUTION Following the Installation Manual perform the drain piping work...

Страница 11: ...apart If the clearance is less than 5 mm it will be hard to remove the drip proof cover and the electrical control box can not be taken out Drain hose Drain pan Heat insulator Hart polyvinyl chloride pipe Adhesion for hart polyvinyl chloride pipe used To connect drain hose on right route it through the knock out for refrigerant piping on AP015 to AP027 model Power supply wire take in port both sid...

Страница 12: ... 19 7 Use two wrenches to connect the indoor unit pipe Use the tightening torque levels as listed in the following table Tightening torque of flare pipe connections Pressure of R410A is higher than that of R22 Approx 1 6 times Therefore using a torque wrench tighten the flare pipe connecting sections which connect the indoor and outdoor units of the specified tightening torque Incorrect connection...

Страница 13: ...ual attached to the outdoor unit Indoor unit power supply For the power supply of the indoor unit prepare the exclusive power supply separated from that of the outdoor unit Arrange the power supply circuit breaker and main switch of the indoor unit connected to the same outdoor unit so that they are commonly used Power supply wire specification Cable 3 core 2 5 mm in conformity with Design 60245 I...

Страница 14: ...ow to remove the electrical control box cover AP015 to AP027 models Take off screws 1 and 2 at this side of the electrical control box and remove the drip proof cover Take off screws 3 and 4 at front side of the electrical control box and remove the electrical control box cover AP036 to AP056 models Take off screws 3 and 4 at front side of the electrical control box and remove the cover of the ele...

Страница 15: ...ayed first When is pushed the indoor unit number displayed following ALL is the header unit 1 6 1 3 2 5 4 Display content varies with the indoor unit model 2 Each time button is pushed indoor unit numbers in the control group change cyclically Select the indoor unit to change settings for The fan of the selected unit runs and the louvers start swinging The indoor unit for change settings can be co...

Страница 16: ...l supplied with the outdoor unit Execute a test run When a fan operation is to be performed for an individual indoor unit turn off the power short CN72 on the circuit board and then turn the power back on First set the operating mode to fan and then operate When the test run has been performed using this method do NOT forget to release the shorting of CN72 after the test run is completed Operate t...

Страница 17: ... once every 3 months Ask a professional for this cleaning maintenance work Such maintenance can extend the life of the product though it involves the owner s expense Failure to clean the indoor and outdoor units regularly will result in poor performance freezing water leakage and even compressor failure Inspection before maintenance Following inspection must be carried out by a qualified installer...

Страница 18: ... be confirmed from both operating status and stop status 1 When and buttons are pushed simultaneously for 4 seconds or more the following display appears If is displayed the mode enters in the error log mode 01 Order of error log is displayed in CODE No Error code is displayed in CHECK Indoor unit address in which an error occurred is displayed in Unit No 2 Every pushing of button used to set temp...

Страница 19: ... side Indoor unit E04 Communication circuit error between indoor outdoor unit Detected at indoor unit side Indoor unit E06 E06 No of indoor units in which sensor has been normally received Decrease of No of indoor units I F E07 Communication circuit error between indoor outdoor unit Detected at outdoor unit side I F E08 E08 Duplicated indoor unit addresses Duplicated indoor unit addresses Indoor u...

Страница 20: ...p 3 side Compressor trouble lock IPDU H03 H03 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side Current detect circuit system error IPDU H04 H04 Comp 1 case thermo operation I F H05 H05 TD1 sensor miswiring I F H06 H06 Low pressure protective operation I F H07 H07 Oil level down detective protection I F H08 H08 01 TK1 sensor error 02 TK2 sensor error 03 TK3 sensor error 04 TK4 sensor error 05 TK5 senso...

Страница 21: ...03 Comp 3 side ALT Phase missing detection Power failure detection Inverter DC voltage error comp Inverter DC voltage error comp Inverter DC voltage error comp I F P07 P07 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side ALT Heat sink overheat error IPDU I F P09 P09 Detected heat storage address ALT No heat storage unit water error Heat storage unit P10 P10 Detected indoor unit address ALT Indoor unit...

Страница 22: ... code name Judging device Central control device indication Outdoor unit 7 segment display Sensor block display of receiving unit Auxiliary code Operation Timer Ready Flash C05 Sending error in TCC LINK central control device TCC LINK C06 Receiving error in TCC LINK central control device TCC LINK C12 Batch alarm of general purpose equipment control interface General purpose equipment I F P30 Alar...

Страница 23: ...Fuji shi Shizuoka ken 416 8521 JAPAN TCF holder TOSHIBA CARRIER EUROPE S A S Route de Thil 01120 Montluel FRANCE Hereby declares that the machinery described below Generic Denomination Air Conditioner Model type MMF AP0156H1 E MMF AP0186H1 E MMF AP0246H1 E MMF AP0276H1 E MMF AP0366H1 E MMF AP0486H1 E MMF AP0566H1 E Commercial name Super Modular Multi System Air Conditioner Super Heat Recovery Mult...

Страница 24: ...tioners is 0 3 kg m3 NOTE 1 If there are 2 or more refrigerating systems in a single refrigerating device the amounts of refrigerant should be as charged in each independent device For the amount of charge in this example The possible amount of leaked refrigerant gas in rooms A B and C is 10 kg The possible amount of leaked refrigerant gas in rooms D E and F is 15 kg NOTE 2 The standards for minim...

Страница 25: ...filter sign If not fill check mark in NO CHANGE and fill check mark in ITEM if changed respectively For check method refer to APPLICABLE CONTROLS in this manual Filter sign lighting time CODE NO 01 NO CHANGE NONE 0000 150H 0001 2500H 0002 5000H 0003 10000H 0004 Filter sign lighting time CODE NO 01 NO CHANGE NONE 0000 150H 0001 2500H 0002 5000H 0003 10000H 0004 Filter sign lighting time CODE NO 01 ...

Страница 26: ...EB99802601 1 ...

Отзывы: