<Precautions during installation>
Use conditions (Case to use in SMMS-i)
• In COOL mode, if temperature of the outside air is under the setup temp. +5.4 °F, FAN status is automatically
made. When temperature of the outside air is under 66 °F, FAN status is also made regardless of the setup
temperature.
• In HEAT mode, if temperature of the outside air is over the setup temp. -5.4 °F, FAN status is automatically
made. When temperature of the outside air is over 59 °F, FAN status is also made regardless of the setup
temperature.
REQUIREMENT
• In “COOL” or “FAN” mode, if temperature of the outside air is under 41 °F, the operation stops automatically in order
to protect the equipment.
In this case, continue the operation by selecting “HEAT” mode.
• In “HEAT” mode, if temperature of the outside air is under 23 °F, the operation stops automatically in order to protect
the equipment.
When operating the air conditioner with the outside air temp. under 23 °F (minimum 5 °F), set temp. of the outside
air to be taken in to 23 °F or upper using a duct heater (locally procured).
For details, consult the dealer which you purchased the air conditioner.