background image

– 17 –

H16

H16

01: TK1 oil circuit system error

02: TK2 oil circuit system error

03: TK3 oil circuit system error

04: TK4 oil circuit system error

Oil level detective circuit error

I/F

H25

H25

TD3 miswiring

I/F

L03

SIM Indoor center unit duplicated

Indoor

L04

L04

SIM Outdoor line address duplicated

I/F

L05

SIM Duplicated indoor units with priority

(Displayed in indoor unit with priority)

I/F

L06

L06 No. of indoor units with priority

SIM Duplicated indoor units with priority

(Displayed in unit other than indoor unit with priority)

I/F

L07

SIM Group line in individual indoor unit

Indoor

L08

L08

SIM Indoor group / Address unset

Indoor, I/F

L09

SIM Indoor capacity unset

Indoor

L10

L10

SIM Outdoor capacity unset

I/F

L17

L17

SIM Outdoor unit model unmatch error

I/F

L20

SIM Duplicated central control addresses

Indoor

L28

L28

SIM Over No. of connected outdoor units

I/F

L29

L29

SIM No. of IPDU error

I/F

L30

L30 Detected indoor address

SIM Indoor outside interlock

Indoor

L31

Extended I/C error

I/F

P01

ALT Indoor fan motor error

Indoor

P03

P03

ALT Discharge temp. TD1 error

I/F

P04

P04

01: Comp. 1 side

02: Comp. 2 side

03: Comp. 3 side

ALT High-pressure SW system operation

IPDU

P05

P05

00: Detected phase loss

ALT

Phase loss error / interruption of power supply

I/F

01: Comp. 1 side

02: Comp. 2 side

03: Comp. 3 side

Inverter DC voltage (Vdc) error

P07

P07

01: Comp. 1 side

02: Comp. 2 side

03: Comp. 3 side

ALT Heat sink overheat error

IPDU, I/F

P10

P10 Detected indoor address

ALT Indoor overflow error

Indoor

P12

ALT Indoor fan motor error or duct setting miss

Indoor

P13

P13

ALT Outdoor liquid back detection error

I/F

P15

P15 01: TS condition

02: TD condition

ALT Gas leak detection

I/F

P17

P17

ALT Discharge temp. TD2 error

I/F

Check code

Wireless remote control

Check code name

Judging device

Wired remote 

control display

Outdoor 7-segment display

Sensor block display of 

receiving unit

Auxiliary code

Operation Timer Ready Flash

A3-IPDU

Fan 

IPDU

1

2

3

01

02

03

04

05

06

07

08

09

0A

0B

0C

0D

0E

0F

 : IPDU error

Error detected by TCC-LINK central control device

TCC-LINK : TOSHIBA Carrier Communication Link.

P18

P18

ALT Discharge temp. TD3 error

I/F

P19

P19 Detected outdoor unit number

ALT 4-way valve inverse error

I/F

P20

P20

ALT High-pressure protective operation

I/F

P22

P22

0

: IGBT circuit

1

: Location detection circuit 

error

3

: Motor lock-up error

4

: Motor current was 

detected.

C

: Abnormal temperature was 

detected by the TH sensor.

D

: TH sensor error

E

: Inverter DC voltage error 

(outdoor unit fan)

Caution)

Although letters 0 to F appear at 

locations indicated by “ ”, 

please ignore them.

ALT Outdoor fan IPDU error

IPDU

P26

P26

01: Comp. 1 side

02: Comp. 2 side

03: Comp. 3 side

ALT G-TR short protection error

IPDU

P29

P29

01: Comp. 1 side

02: Comp. 2 side

03: Comp. 3 side

ALT Comp position detective circuit system error

IPDU

P31

P31

ALT Other indoor unit error 

(Group follower unit error)

Indoor

Check code

Wireless remote control

Check code name

Judging device

Wired remote 

control display

Outdoor 7-segment display

Sensor block display of 

receiving unit

Auxiliary code

Operation Timer Ready Flash

C05

Sending error in TCC-LINK central control device

TCC-LINK

C06

Receiving error in TCC-LINK central control device

TCC-LINK

C12

Batch alarm of general-purpose equipment control 

interface

General-purpose 

equipment I/F

P30

Differs according to error contents of unit with occurrence of alarm Group control branching unit error

TCC-LINK

(L20 is displayed)

Duplicated central control addresses

Check code

Wireless remote control

Check code name

Judging device

Wired remote 

control display

Outdoor 7-segment display

Sensor block display of 

receiving unit

Auxiliary code

Operation Timer Ready Flash

33-EN

34-EN

+00EH99881801_01EN.book  Page 17  Friday, November 25, 2011  10:23 AM

Содержание MMD-AP00244BH2UL

Страница 1: ...L MMD AP0304BH2UL MMD AP0364BH2UL MMD AP0424BH2UL MMD AP0484BH2UL Indoor Unit Model name Medium Static Ducted Type MMD AP0074BH2UL MMD AP0094BH2UL MMD AP0124BH2UL MMD AP0154BH2UL MMD AP0184BH2UL MMD AP0214BH2UL AIR CONDITIONER MULTI TYPE Installation Manual 00EH99881801_01EN book Page 1 Friday November 25 2011 10 23 AM ...

Страница 2: ...use any refrigerant different from the one specified for complement or replacement Otherwise abnormally high pressure may be generated in the refrigeration cycle which may result in a failure or explosion of the product or an injury to your body Connect ground wire grounding work Incomplete grounding may cause an electric shock Do not connect ground wires to gas pipes water pipes lightning rods or...

Страница 3: ...oes not enter the refrigerating cycle To prevent charging an incorrect refrigerant and refrigerating oil the sizes of connecting sections of charging port of the main unit and installation tools are changed from those for the conventional refrigerant Accordingly the exclusive tools are required for the new refrigerant R410A For connecting pipes use new and clean piping designed for R410A and pleas...

Страница 4: ...ncies are generated by inverter equipment in house power generators medical equipment or communication equipment Malfunctioning or control trouble in the air conditioner or noise may adversely affect the equipment s operation Locations where there is anything under the unit installed that would be compromised by wetness If the drain has become blocked or when the humidity is over 80 condensation f...

Страница 5: ... opening size C 23 6 600 41 3 1050 55 1 1400 Space required for attaching or detaching the filter D 23 6 600 23 6 600 40 5 1030 Electrical control box Air filter locally procured 5 9 150 Ceiling opening size 15 5 400 Min 1 Air discharge Ceiling opening size C Electrical control box Check port A 17 7 17 7 450 450 Air discharge 5 9 150 or more Air intake 1 2 30 Ceiling Ceiling Unit width 31 5 800 Ce...

Страница 6: ...th plastic band at positions other than specified To install vibration isolation material to hanging bolts confirm that it does not increase the unit vibration External dimensions Unit in mm GOOD NO GOOD NO GOOD 1 room Hanging bolt 4 M0 4 10 locally procured Hanging bolt pitch B Unit external dimension A Air discharge flange outside C 5 5 140 1 7 44 1 9 49 Outside 8 6 218 2 5 8 147 5 Air filter sl...

Страница 7: ...ir intake and air discharge sides are within 0 2 5 mm with each other Set the drain pipe connecting port side within 0 2 5 mm lower than opposite side Front view Side view 0 2 5 mm or less 0 2 5 mm or less Installation of wireless remote control sold separately For installation of the wireless remote control refer to the instructions that are supplied with the control The connection point for the ...

Страница 8: ...emporarily with the screws indicated by the arrows for protection when shipped After reattaching it seal the screw holes with tape instead of using the screws Cover plate for filter slot Cover plate fixing screws 2 Pull out the filter rack and set the air filter locally procured in it 3 Push the filter rack in fully and reattach the cover plate Screws x 2 Filter rack Air filter locally procured Ai...

Страница 9: ...leaks or if the condensate water does not flow normally the problem should be diagnosed and corrected before the system is certified for operation In the test run check that water drain is properly performed and water does not leak from the connecting part of the pipes When doing this also check that no abnormal sounds are heard from the drain pump motor Check draining also when installed in heati...

Страница 10: ...rovided with the unit or the one used for the R410A refrigerant The flaring dimensions for R410A are different from the ones used for the conventional R22 refrigerant A new flare tool manufactured for use with the R410A refrigerant is recommended but the conventional tool can still be used if the projection margin of the copper pipe is adjusted to be as shown in the following table Projection marg...

Страница 11: ... exothermic fire or malfunction 2 Connect ground wire grounding work Incomplete grounding cause an electric shock Do not connect ground wires to gas pipes water pipes lightning rods or ground wires for telephone wires 3 Install appliance in accordance with national wiring regulations Capacity shortage of circuit breaker or incomplete installation may cause an electric shock or a fire CAUTION Consu...

Страница 12: ...of wireless type included Up to 1312 4 400 m Total wire length of remote control inter unit wiring L1 L2 Ln Up to 656 2 200 m L1 L L2 Ln Indoor unit Remote control inter unit wiring Indoor unit Indoor unit Indoor unit Remote control Max 8 units Remote control wiring CAUTION The remote control wire Communication line and AC208 230 V wires cannot be parallel to contact each other and cannot be store...

Страница 13: ...ower has been turned on before the remote control becomes available for operations This is normal and is not indicative of trouble Concerning the automatic addresses The automatic addresses are set up by performing operations on the outdoor interface circuit board While the automatic addresses are being set up no remote control operations can be performed Setup takes up to 10 minutes usually about...

Страница 14: ...the SET DATA of procedure 4 select a SET DATA of the external static pressure to be set up from the following table Change on wired remote control SET DATA External static pressure 0000 Standard Factory default 0001 High static pressure 1 0003 High static pressure 2 0006 Low static pressure With a remote control less system group control Besides the switching method using the wired remote control ...

Страница 15: ...Filter sign term 0000 None 0001 150 H 0002 2500 H Factory default 0003 5000 H 0004 10000 H SET DATA Detection temperature shift value 0000 No shift 0001 1 8 F 1 C 0002 3 6 F 2 C Factory default 0003 5 4 F 3 C 0004 7 2 F 4 C 0005 9 0 F 5 C 0006 10 8 F 6 C SET DATA 0000 0001 remote control sensor Not used Factory default Used 9 Test run Before test run Before turning on the power supply carry out th...

Страница 16: ...LOW or block the air vent Small screw Nameplate Notch M4 25 screw 2 pieces Spacer Receiver unit 10Troubleshooting Confirmation and check When an error occurred in the air conditioner the check code and the indoor UNIT No appear on the display part of the remote control The check code is only displayed during the operation If the display disappears operate the air conditioner according to the follo...

Страница 17: ...ted units Capacity over No of connected indoor units Combined capacity of indoor units exceeds 120 of combined capacity of outdoor units I F E18 Communication error between indoor units Indoor E19 E19 00 Header is nothing 02 Two or more header units Outdoor header units quantity error I F E20 E20 01 Outdoor of other line connected 02 Indoor of other line connected Other line connected during autom...

Страница 18: ...evice Wired remote control display Outdoor 7 segment display Sensor block display of receiving unit Auxiliary code Operation Timer Ready Flash A3 IPDU Fan IPDU 1 2 3 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0F IPDU error Error detected by TCC LINK central control device TCC LINK TOSHIBA Carrier Communication Link P18 P18 ALT Discharge temp TD3 error I F P19 P19 Detected outdoor unit number ALT 4 ...

Страница 19: ...g systems in a single refrigerating device the amounts of refrigerant should be as charged in each independent device For the amount of charge in this example The possible amount of leaked refrigerant gas in rooms A B and C is 22 lbs 10 kg The possible amount of leaked refrigerant gas in rooms D E and F is 33 lbs 15 kg NOTE 2 The standards for minimum room volume are as follows 1 No partition shad...

Страница 20: ...IGH STATIC 1 0001 HIGH STATIC 2 0003 LOW STATIC 0006 Have you changed lighting time of filter sign If not fill check mark in NO CHANGE and fill check mark in ITEM if changed respectively For check method refer to Applicable controls in this manual Filter sign lighting time CODE No 01 NO CHANGE NONE 0000 150H 0001 2500H 0002 5000H 0003 10000H 0004 Filter sign lighting time CODE No 01 NO CHANGE NONE...

Отзывы: