Toshiba MMD-AP00244BH2UL Скачать руководство пользователя страница 13

– 12 –

EN

Wire connection

REQUIREMENT

• Connect the wires matching the terminal numbers. 

Incorrect connection causes a trouble.

• Pass the wires through the bushing of wire connection 

holes of the indoor unit.

• The low-voltage circuit is provided for the remote 

control. (Do not connect the high-voltage circuit)

• Remove the cover of the electrical control box by 

taking off the mounting screws (3 positions).

• Attach the conduit pipe with a lock nut.
• Tighten the screws of the terminal block, and fix the 

wires with cord clamp attached to the electrical 
control box.
(Do not apply tension to the connecting section of the 
terminal block.)

• Mount the cover of the electrical control box without 

pinching wires.

Power supply wires and 
ground wire

1. Strip the wire ends. 

Power supply wire: 0.4” (10 mm)
Ground wire: 0.8” (20 mm)

2. Match the wire colors with the terminal numbers on 

the indoor units’ and circuit breakers’ terminal blocks 
and firmly screw the wires to the corresponding 
terminals.

3. Secure the ground wire with the ground screw.
4. Fix the wires with a cord clamp.

Unit: in (mm)

CAUTION

Firmly tighten the screws of the terminal block.

Keep the wire length as shown in figure below when it 
is connected to the terminal block.

Address setup

Set up the addresses as per the Installation Manual 
supplied with the outdoor unit.

Control wire hole

Electrical control box cover

Screw

Screw

Conduit 

connection 

hole

B

A

L
L

Ground screw

Cord clamp

Conduit pipe

Control wire / 

Remote control 

terminal block

Power supply 

wires and 

ground wire

Control wire 

(2-core 

shielded wire)

Power supply 

terminal block

Remote 

control wire

Cord 

clamp

Lock nut

L

1

L

2

0.8” (20)

1.2” (30)

0.4” (10)

Ground wire

0.

08

” (2

) or

 le

ss

Power supply wires and control 

wire

8

Applicable controls

REQUIREMENT

When the air conditioner is used for the first time, it will 
take some moments after the power has been turned on 
before the remote control becomes available for 
operations: This is normal and is not indicative of trouble.
• Concerning the automatic addresses (The automatic 

addresses are set up by performing operations on the 
outdoor interface circuit board.)
While the automatic addresses are being set up, no 
remote control operations can be performed. Setup 
takes up to 10 minutes (usually about 5 minutes).

• When the power is turned on after automatic address 

setup
It takes up to 10 minutes (usually about 3 minutes) for 
the outdoor unit to start operating after the power has 
been turned on.

Before the air conditioner was shipped from the factory, 
all units are set to [STANDARD] (factory default). If 
necessary, change the indoor unit settings.

The settings are changed by operating the wired remote 
control.

* The settings cannot be changed using only a 

wireless remote control, simple remote control or 

group control remote control by itself so install a 

wired remote control separately as well.

Basic procedure for changing 
settings

Change the settings while the air conditioner is not 
working. 

(Stop the air conditioner before making 

settings.)

CAUTION

Set only the CODE No. shown in the following table: Do 
NOT set any other CODE No.
If a CODE No. not listed is set, it may not be possible to 
operate the air conditioner or other trouble with the 
product may result.

1

Push and hold 

 button and “TEMP.” 

 

button simultaneously for at least 4 
seconds. After a while, the display flashes 
as shown in the figure. Confirm that the 
CODE No. is [01].

If the CODE No. is not [01], push 

 button to clear 

the display content, and repeat the procedure from 
the beginning. (No operation of the remote control 
is accepted for a while after 

 button is pushed.)

(While air conditioners are operated under the 
group control, “ALL” is displayed first. When 

 is pushed, the indoor unit number 

displayed following “ALL” is the header unit.)

1

6

1

3

2

5

4

(* Display content varies with the indoor unit 

model.)

23-EN

24-EN

+00EH99881801_01EN.book  Page 12  Friday, November 25, 2011  10:23 AM

Содержание MMD-AP00244BH2UL

Страница 1: ...L MMD AP0304BH2UL MMD AP0364BH2UL MMD AP0424BH2UL MMD AP0484BH2UL Indoor Unit Model name Medium Static Ducted Type MMD AP0074BH2UL MMD AP0094BH2UL MMD AP0124BH2UL MMD AP0154BH2UL MMD AP0184BH2UL MMD AP0214BH2UL AIR CONDITIONER MULTI TYPE Installation Manual 00EH99881801_01EN book Page 1 Friday November 25 2011 10 23 AM ...

Страница 2: ...use any refrigerant different from the one specified for complement or replacement Otherwise abnormally high pressure may be generated in the refrigeration cycle which may result in a failure or explosion of the product or an injury to your body Connect ground wire grounding work Incomplete grounding may cause an electric shock Do not connect ground wires to gas pipes water pipes lightning rods or...

Страница 3: ...oes not enter the refrigerating cycle To prevent charging an incorrect refrigerant and refrigerating oil the sizes of connecting sections of charging port of the main unit and installation tools are changed from those for the conventional refrigerant Accordingly the exclusive tools are required for the new refrigerant R410A For connecting pipes use new and clean piping designed for R410A and pleas...

Страница 4: ...ncies are generated by inverter equipment in house power generators medical equipment or communication equipment Malfunctioning or control trouble in the air conditioner or noise may adversely affect the equipment s operation Locations where there is anything under the unit installed that would be compromised by wetness If the drain has become blocked or when the humidity is over 80 condensation f...

Страница 5: ... opening size C 23 6 600 41 3 1050 55 1 1400 Space required for attaching or detaching the filter D 23 6 600 23 6 600 40 5 1030 Electrical control box Air filter locally procured 5 9 150 Ceiling opening size 15 5 400 Min 1 Air discharge Ceiling opening size C Electrical control box Check port A 17 7 17 7 450 450 Air discharge 5 9 150 or more Air intake 1 2 30 Ceiling Ceiling Unit width 31 5 800 Ce...

Страница 6: ...th plastic band at positions other than specified To install vibration isolation material to hanging bolts confirm that it does not increase the unit vibration External dimensions Unit in mm GOOD NO GOOD NO GOOD 1 room Hanging bolt 4 M0 4 10 locally procured Hanging bolt pitch B Unit external dimension A Air discharge flange outside C 5 5 140 1 7 44 1 9 49 Outside 8 6 218 2 5 8 147 5 Air filter sl...

Страница 7: ...ir intake and air discharge sides are within 0 2 5 mm with each other Set the drain pipe connecting port side within 0 2 5 mm lower than opposite side Front view Side view 0 2 5 mm or less 0 2 5 mm or less Installation of wireless remote control sold separately For installation of the wireless remote control refer to the instructions that are supplied with the control The connection point for the ...

Страница 8: ...emporarily with the screws indicated by the arrows for protection when shipped After reattaching it seal the screw holes with tape instead of using the screws Cover plate for filter slot Cover plate fixing screws 2 Pull out the filter rack and set the air filter locally procured in it 3 Push the filter rack in fully and reattach the cover plate Screws x 2 Filter rack Air filter locally procured Ai...

Страница 9: ...leaks or if the condensate water does not flow normally the problem should be diagnosed and corrected before the system is certified for operation In the test run check that water drain is properly performed and water does not leak from the connecting part of the pipes When doing this also check that no abnormal sounds are heard from the drain pump motor Check draining also when installed in heati...

Страница 10: ...rovided with the unit or the one used for the R410A refrigerant The flaring dimensions for R410A are different from the ones used for the conventional R22 refrigerant A new flare tool manufactured for use with the R410A refrigerant is recommended but the conventional tool can still be used if the projection margin of the copper pipe is adjusted to be as shown in the following table Projection marg...

Страница 11: ... exothermic fire or malfunction 2 Connect ground wire grounding work Incomplete grounding cause an electric shock Do not connect ground wires to gas pipes water pipes lightning rods or ground wires for telephone wires 3 Install appliance in accordance with national wiring regulations Capacity shortage of circuit breaker or incomplete installation may cause an electric shock or a fire CAUTION Consu...

Страница 12: ...of wireless type included Up to 1312 4 400 m Total wire length of remote control inter unit wiring L1 L2 Ln Up to 656 2 200 m L1 L L2 Ln Indoor unit Remote control inter unit wiring Indoor unit Indoor unit Indoor unit Remote control Max 8 units Remote control wiring CAUTION The remote control wire Communication line and AC208 230 V wires cannot be parallel to contact each other and cannot be store...

Страница 13: ...ower has been turned on before the remote control becomes available for operations This is normal and is not indicative of trouble Concerning the automatic addresses The automatic addresses are set up by performing operations on the outdoor interface circuit board While the automatic addresses are being set up no remote control operations can be performed Setup takes up to 10 minutes usually about...

Страница 14: ...the SET DATA of procedure 4 select a SET DATA of the external static pressure to be set up from the following table Change on wired remote control SET DATA External static pressure 0000 Standard Factory default 0001 High static pressure 1 0003 High static pressure 2 0006 Low static pressure With a remote control less system group control Besides the switching method using the wired remote control ...

Страница 15: ...Filter sign term 0000 None 0001 150 H 0002 2500 H Factory default 0003 5000 H 0004 10000 H SET DATA Detection temperature shift value 0000 No shift 0001 1 8 F 1 C 0002 3 6 F 2 C Factory default 0003 5 4 F 3 C 0004 7 2 F 4 C 0005 9 0 F 5 C 0006 10 8 F 6 C SET DATA 0000 0001 remote control sensor Not used Factory default Used 9 Test run Before test run Before turning on the power supply carry out th...

Страница 16: ...LOW or block the air vent Small screw Nameplate Notch M4 25 screw 2 pieces Spacer Receiver unit 10Troubleshooting Confirmation and check When an error occurred in the air conditioner the check code and the indoor UNIT No appear on the display part of the remote control The check code is only displayed during the operation If the display disappears operate the air conditioner according to the follo...

Страница 17: ...ted units Capacity over No of connected indoor units Combined capacity of indoor units exceeds 120 of combined capacity of outdoor units I F E18 Communication error between indoor units Indoor E19 E19 00 Header is nothing 02 Two or more header units Outdoor header units quantity error I F E20 E20 01 Outdoor of other line connected 02 Indoor of other line connected Other line connected during autom...

Страница 18: ...evice Wired remote control display Outdoor 7 segment display Sensor block display of receiving unit Auxiliary code Operation Timer Ready Flash A3 IPDU Fan IPDU 1 2 3 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0F IPDU error Error detected by TCC LINK central control device TCC LINK TOSHIBA Carrier Communication Link P18 P18 ALT Discharge temp TD3 error I F P19 P19 Detected outdoor unit number ALT 4 ...

Страница 19: ...g systems in a single refrigerating device the amounts of refrigerant should be as charged in each independent device For the amount of charge in this example The possible amount of leaked refrigerant gas in rooms A B and C is 22 lbs 10 kg The possible amount of leaked refrigerant gas in rooms D E and F is 33 lbs 15 kg NOTE 2 The standards for minimum room volume are as follows 1 No partition shad...

Страница 20: ...IGH STATIC 1 0001 HIGH STATIC 2 0003 LOW STATIC 0006 Have you changed lighting time of filter sign If not fill check mark in NO CHANGE and fill check mark in ITEM if changed respectively For check method refer to Applicable controls in this manual Filter sign lighting time CODE No 01 NO CHANGE NONE 0000 150H 0001 2500H 0002 5000H 0003 10000H 0004 Filter sign lighting time CODE No 01 NO CHANGE NONE...

Отзывы: