Connecting drain pipe
The following materials for piping work and insulating process are procured locally.
REQUIREMENT
• Using adhesive agent for vinyl chloride, connect the hard vinyl chloride pipes certainly so that water does not leak.
• It requires several times to dry and harden the adhesive agent.
(Refer to Guide Manual of the adhesive agent.)
In this time, be sure not to apply force to the connecting section with the drain pipes.
Piping method
Drain and refrigerant pipes can be drew out from left, right, back or bottom depending on the installation location.
However, drain pipes can be drew out from left only when the refrigerant pipes are drew out from left. The drain
hose must be fix to the refrigerant pipe with banding band and installed with gradient of 1/100 or more. The drain
hose end connected to the indoor unit must be free from external force.
• Do not route the drain hose and refrigerant pipes on the electrical control box. Dew condensation water from
pipes may enter into the electrical control box and it may cause malfunction. Exclude AP015 to AP027 model.
• Keep the drain hose and refrigerant pipes clear of the electrical control box 5 mm or more on AP015 to AP027
model. If the clearance is less than 5 mm, drip-proof cover cannot be removed and the electrical control box
cannot be took out.
Drain hose
Drain pan
Heat insulator
Hart polyvinyl chloride pipe
Adhesion for hart polyvinyl
chloride pipe used
To connect drain hose on
right, route it through the
knock-out for refrigerant
piping on AP015 to AP027
model.
Power supply wire take-in
port (both sides)
Refrigerant pipe connecting
port (both sides)
Piping port at
back
Piping port at bottom
Drain hose connecting port
(both sides)
*AP036 to AP056 only
Check the draining
• After piping work, remove the air intake grille and pour water in the drain pan to check water drain and water
leakage from connecting part of the drain hose.
• After check of the water drain, attach the air intake grille as before.
Fix the drain hose to the refrigerant pipe
with binding bands without hanging down
and slack. fix 3 points
Do not bind the drain hose and refrigerant
pipe (heat insulator) too tight.
Drain hose
Drain pan
• To connect drain hose on left
PVC pipe
(Drain piping)
• To connect drain hose on right
Drain pan
Drain hose
Fix with banding band.
Heat
insulator
Heat insulator
*Connect and fix drain pipe at outside of the unit on site.
Install the drain hose with gradient of 1/100 or more to
connect it to unit on both left and right sides.
Refrigerant
piping
PVC pipe
(Drain piping)
15-EN
16-EN