Typical Start Current Requirements
300%
350%
400%
450%
Agitator
—
Atomiser
—
Bottle Washer
—
Centrifuge
—
Chipper
—
Compressor - Recip (loaded)
—
Compressor - Recip (unloaded)
—
Compressor - Screw (loaded)
—
Compressor - Screw (unloaded)
—
Conveyor - Belt
—
Conveyor - Roller
—
Conveyor - Screw
—
Crusher - Cone
—
Crusher - Jaw
—
Crusher - Rotary
—
Crusher - Vertical Impact
—
Debarker
—
Dryer
—
Dust Collector
—
Edger
—
Fan - Axial (Damped)
—
Fan - Axial (Un-damped)
—
Fan - Centrifugal (Damped)
—
Fan - Centrifugal (Un-damped)
—
Fan - High Pressure
—
Grinder
—
Hydraulic Power Pack
—
Mill
—
Mill - Ball
—
Mill - Hammer
—
Mill - Roller
—
Mixer
—
Palletiser
—
Planer
—
Press
—
Pump - Bore
—
Pump - Centrifugal
—
Pump - Positive Displacement
—
Pump - Slurry
—
Re-pulper
—
Rotary Table
—
Sander
—
Saw - Bandsaw
—
Saw - Circular
—
Separator
—
Shredder
—
Slicer
—
Tumbler
—
The above table is intended as a guide only. Individual machine
and motor characteristics will determine the actual start current
requirements.
10.2
AC53a Utilisation Codes
AC53a Utilisation Category Format
78 A: AC-53a 3.5-15 : 50-10
Starter Current Rating
(Amps)
Start Current
(multiple of FLC)
Start Time
(seconds)
On-load Duty Cycle
(% )
Starts Per Hour
Starter Current Rating
: The Full Load Current rating of soft
starter given the parameters detailed in the remaining sections
of the utilisation code.
Start Current
: The maximum available start current given the
parameters detailed in the remaining sections of the utilisation
code.
Start Time
: The maximum available start time given the
parameters detailed in the remaining sections of the utilisation
code.
On-load Duty Cycle
: The maximum permissible percentage of
each operating cycle that the soft starter can operate given the
parameters detailed in the remaining sections of the utilisation
code.
Starts Per Hour
: The maximum available number of starts per
hour given the parameters detailed in the remaining sections of
the utilisation code.
10.3
AC53b Utilisation Codes
AC53b Utilisation Category Format
90 A: AC-53b 3.5-15 : 345
Starter Current Rating
(Amps)
Start Current
(multiple of FLC)
Start Time
(seconds)
Off Time
(seconds)
Starter Current Rating
: The Full Load Current rating of soft
starter given the parameters detailed in the remaining sections
of the utilisation code.
Start Current
: The maximum available start current given the
parameters detailed in the remaining sections of the utilisation
code.
Start Time
: The maximum available start time given the
parameters detailed in the remaining sections of the utilisation
code.
Off Time
: The minimum allowable time between end of one start
and the beginning of the next start given the parameters detailed
in the remaining sections of the utilisation code.