APPLICATION EXAMPLES
28
ME00070B
TMS7 SERIES
8.4 Two Speed Motors
I34
I33
LEGEND
K2A
K1M
REMO TE START RELAY (HIGH SPEED)
LINE CONTACTOR (HIGH SPEED)
K1A
REMOTE START RELAY (LOW SPEED)
K2M
K3M
S1
LINE CONTACT OR (LO W SPEED)
STAR CONTACT OR (HIGH SPEED)
RESET PUSHBUTT ON
NOTES
CONTACTORS K2M AND K3M MUST BE
MECHANICALLY INTERLOCKED.
1.
K1A
K2A
K1A
K2A
REMOTE LOW SPEED
START INPUT
REMOTE HIGH SPEED
START INPUT
K3M
K1A
K2M
K2A
OUT PUT C
R11
R14
R12
A3
THERM.
A1
A2
SUPPLY
MOT OR
THERMISTOR
K1M
C2
C1
T1
T2
T3
E
L1
L2
L3
L1B
L3B
L2B
3 PHASE
SUPPLY
K3M
K2M
T4
T5
T6
T 1
T2
T3
TO DUAL SPEED MOTOR
DAHLANDER T YPE
SEE NOT E1.
K1M
K3M
K2M
K3M
K1M
CONTROL SUPPLY
CONTROL
SUPPLY
FLC SELECT
K1A
I44
I43
START
K1M
RESET
STO P
K2M
S1
I22
I21
I12
I11
Description:
The TMS7 can be configured for control of dual speed Dahlander type motors. In this application the TMS7 is employed with a High Speed
contactor (K1M), Low Speed contactor (K2M) and a Star contactor (K3M).
On receipt of a High Speed start signal the High Speed contactor (K1M) and Star contactor (K3M) are closed. The TMS7 then controls the
motor according to the Primary Motor Parameter set. (Function Numbers 1~9)
On receipt of a Low Speed start signal the Low Speed contactor (K2M) is closed. The relay contact across Input A is also closed causing
the TMS7 to control the motor according to the Secondary Parameter set (Function Numbers 80~88).
Function Settings:
-
Function 23.
Relay Output C Functionality
= 0 (Assigns the Trip function to Relay Output C)