PROGRAMMING
18
ME00070B
TMS7 SERIES
7.2
Function List
No.
Function
Primary Motor Settings
Default
Setting
1
Motor full load current
-
2
Current limit
350
3
Minimum current
350
4
Start ramp time
1
5
Stop ramp time
0
6
Motor trip class
10
7
Current imbalance sensitivity
5
8
Undercurrent protection
20
9
Stall protection
400
Start/Stop Formats
10 Soft stop mode
0
Starter Functionality
20 Local/Remote operation
0
21 Relay output A functionality
11
22 Relay output B functionality
10
23 Relay output C functionality
0
Protection Settings
30 Phase rotation
0
31 Restart delay
15
32 Current imbalance
0
Set Points
40 Low current alarm
50
41 High current alarm
105
42 Motor temperature alarm
80
43 Field calibration
100
Analogue Output (Motor Current - % FLC)
50 4-20mA output range - max
100
51 4-20mA output range - min
0
Serial Communications
60 RS485 timeout
0
61 RS485 baud rate
4
62 RS485 satellite address
20
Auto Reset
70 Auto-reset - configuration
0
71 Auto-reset - number of resets
1
72 Auto-reset - group A & B delay
5
73 Auto-reset - group C delay
5
Secondary Motor Settings
80 Motor full load current
-
81 Current limit
350
82 Minimum current
350
83 Start ramp time
1
84 Stop ramp time
0
85 Motor trip class
10
86 Current imbalance sensitivity
5
87 Undercurrent protection
20
88 Stall protection
400
Protection Delays
90 Current imbalance trip delay
3
Read Only Data
100 Model Number
-
101 Fault History
-
Restricted Functions
110 Access code
0
111 Update access code
0
112 Function lock
0
113 Restore function settings
0
7.3
Function Descriptions
1.
Motor Full Load Current
Range
: Model Dependant (Amps)
Default Setting
: Model Dependant (Amps)
Description
: Sets the TMS7 for the connected motor’s full load
current.
Adjustment
: Set to the Full Load Current (amps) rating shown
on the motor nameplate.
2.
Current Limit
Range
: 100 – 550 % FLC
Default Setting
: 350% FLC
Description
: Sets the current limit for the Constant Current start
mode.
700%
500%
300%
100%
50%
100%
ROTOR SPEED
( % Full Speed)
eg. Function 2.
Current Limit
= 350% x FLC
Adjustment
: The required setting for the Current Limit function
is installation dependant and should be set such that:
•
The motor is supplied with sufficient start current to enable
it to produce torque adequate to easily accelerate the
connected load.
•
Desired starting performance is obtained.
•
TMS7 ratings are not exceeded.
3.
Minimum Current
Range
: 100 – 550 % FLC
Default Setting
: 350% FLC
Description
: Sets the minimum current level for the Ramp Start
mode.
700%
500%
300%
100%
50%
100%
ROTOR SPEED
(% Full Speed)
Function. 2
Current Limit
= 350% x FLC
Function. 3
Minimum Current
= 200% x FLC
Function. 4
Start Ramp Time
= 10 secs