57
<SW07 Bit 2 OFF (two-step control)>
Power peak-cut control is enabled as long as SW1, as shown on the wiring diagram, is ON (continuously).
Note 1: Specifications of display relay contact
The terminal for display output ([Operation] terminal) must satisfy the following electrical rating.
When connecting a conductive load (e.g. relay coil) to the display relay load, insert a surge killer CR (for an AC
power supply) or a diode for preventing back electromotive force (for a DC power supply) on the bypass circuit.
7-3-3. Power peak-cut control (extended)
Operation
An external power peak-cut control signal limits the peak capacity of the outdoor unit.
L1: Power peak-cut control indication lamp
SW1: Power peak-cut control ON switch*1
SW2: Power peak-cut control OFF switch*1
*1 The inputs of SW1 and SW2 can be either pulse (100 msec or wider) or step signals.
* Be sure to provide a contact for each terminal.
Extended power peak-cut control settings
Specifications of display relay contact
Note 1: Specifications of display relay contact
The terminal for display output ([Operation] terminal) must satisfy the following electrical rating.
When connecting a conductive load (e.g. relay coil) to the display relay load, insert a surge killer CR (for an AC
power supply) or a diode for preventing back electromotive force (for a DC power supply) on the bypass circuit.
Jumper wire
J20
Input
SW1
y
a
l
e
r
r
o
t
a
c
i
d
n
I
1
t
i
B
7
0
W
S
)
1
L
(
N
O
1
t
i
B
F
F
O
1
t
i
B
Cut
0 % (forced stop)
60 % capacity (upper limit regulated)
100 % (normal operation)
100 % (normal operation)
<Electrical Rating>
220 to 240 VAC, 10 mA or more, 1 A or less
24 VDC, 10 mA or more, 1 A or less (non-conductive load)
Indication lamp
External power peak-cut control
signals
Peak capacity
I/F SW07 Bit 1
N
O
F
F
O
2
W
S
1
W
S
1
L
OFF
OFF
OFF
100 % (normal operation)
100 % (normal operation)
ON
ON
OFF
80 % (upper limit regulated)
85 % (upper limit regulated)
ON
OFF
ON
60 % (upper limit regulated)
75 % (upper limit regulated)
ON
ON
ON
0 % (forced stop)
60 % (upper limit regulated)
<Electrical Rating>
220 to 240 VAC, 10 mA or more, 1 A or less
24 VAC, 10 mA or more, 1 A or less (non-conductive load)
Outdoor unit
L1: Display lamp ensuring power peak cut control
Locally procured
Outdoor unit
interface PCB
CN513
SW07
Bit 2 OFF
Connection cable
Optional PCB
Display
relay
TB1
TB2
PJ17
COM
ON
OFF
COM
[ON]
[OFF]
[OPERATION]
Shield wire
Power
supply
L1
SW1
Shield wire
SW2
For SW1 and SW2, be sure to provide
no-voltage contacts for each terminal.
ON
OFF
ON
OFF
41
A10-1510.indb 41
A10-1510.indb 41
2016/04/08 17:20:51
2016/04/08 17:20:51
AMP Air Conditioning
www.ampair.co.uk | [email protected]