(2)Clearing error by using switches on the interface board of the outdoor unit
Using the switches on the interface P.C. board of the outdoor unit, this function is to clear the currently detected
error for each refrigerant circuit system without resetting the power supply.
Errors in both outdoor and indoor units are once cleared, and error detection is performed again.
Set the rotary switches on the interface P.C. board of the
outdoor unit as follows.
Set SW01 / SW02 / SW03 to [2/16/1]
7-segment display
Press the push-switch SW04 on the same board for
5 to 10 seconds.
[ C L] is displayed in 7-segment display [B] on the board
(for 5 seconds), and the error is completely cleared.
7-segment display
.
.
.
(3)Clearing error by resetting power
This function is provided to clear error in a system by resetting the power of all the outdoor and the indoor units.
As same as the clearing method by the interface P.C. board, errors of both the outdoor and the indoor units are
once cleared, and error detection is performed again.
<Method>
(1) Be sure to reset power of both the outdoor and the indoor units.
(2) Turn on the power of the indoor unit prior to the power of the outdoor unit.
NOTE)
After power reset, it requires usually 3 minutes to power-on due to the initial communication of the
system. In some cases, it requires max. 10 minutes.
SW09
SW07
SW11
SW06
SW10
SW12 SW13
SW16
SW14
SW17
D600 D601 D602 D603 D604
SW04
SW05
SW15
SW01
SW02
SW03
SW30
D600 D601 D602 D603 D604
SW04
SW05
SW15
SW01
SW02
SW03
Interface P.C. board
Push switch
7-segment
display [A]
Push switch
7-segment
display [B]
Rotary switches
77