11
6. Transducer installation
- To minimize measurement errors arising from flow profile, a straight pipe run is necessary for
transducer installation.
- Liquid should fill the pipes completely and transducers should be installed in locations which
have no air bubbles.
- For measurements in underground piping, the usual means is to locate the flowmeter in a pit to
facilitate transducer installation, maintenance, and testing.
L
≧
10D
10D
or
more
Probe
L
≧
5D
10D
or more
L
≧
50D
10D
L
≧
10D
L
≧
30D
D
0.5D
1.5D
L
≧
5D
L
≧
5D
L
≧
10D
L
≧
30D
Flow Control at upper side
L
≧
10D
P
L
≧
50D
Upstream straight pipe length
Downstream straight pipe length
Structural
condition
90°bend
T shape joint
Increasing
Diameter
Control
Valves
Pump
[Refer to JEMIS 032- 1987 ]
Reducing
Diameter
Flow Control at lower side
Stop Valve
Checkvalve
D : Pipe Diameter