Page 46
MAINTENANCE
The moving joints should be occasionally
lubricated with a light coat of Toshiba
grease.
INTERLOCKS
Circumvent the handle interlock by
pushing a screwdriver through the slot
and operate the handle several times.
Check that the CPI electrical interlock
(microswitch) operates each time the
handle is moved.
The CPI (control
p o w e r
interlock)
should
c l o s e
approximately
before the handle
reaches the full ON position. As the
handle is moved from ON to OFF, the
CPI switch should open by the time the
handle has moved approximately 1
or one inch (Fig. 59).
Check that the handle interlock to the
vacuum
contactor operates freely.
Lubricate with Toshiba B8 grease if
necessary.
Refer to the GENERAL
DESCRIPTION section for the location
of the handle mechanical interlocks and
the CPI electrical interlock.
LOAD RECEPTACLE
The load receptacle requires little maintenance
other than periodic cleaning and inspection.
Using a clean, dry cloth, wipe off the
surfaces of the load receptacle insulator
and the insulating drive links.
Operate the release lever to check for
free movement of the bolted pressure
mechanism.
Do not
attempt to change
t h e t o r q u e s e t t i n g s o f t h e b o l t e d
pressure clip assembly.
I S W I T C H A C T U A T I O N
S W I T C H
ENGAGE,’
I
O F F
O P E N ]
Fig. 59 Interlock Sequence Check