OPERATION
Page 39
The release lever
must be pushed in
(Fig. 48)
before the isolation switch is closed or the
controller is operated under load. The medium
voltage compartment door cannot be closed
unless the release lever is pushed in. A
mechanical interlock prevents the isolation
switch from being closed unless the medium
voltage door is closed.
Release lever must be
pushed in and latched
before
operating
the
controller.
INITIAL
Energizing a medium voltage controller or line-
up of controllers for the first time is potentially
dangerous.
Therefore
only
qualified
personnel
as defined in the SAFETY section of this
manual,
should energize
the
equipment
(Fig. 49). If faults caused by damage or poor
installation practices have not been detected in
the PRE-ENERGIZATION CHECK section, major
damage including personal injury can result
when the power is applied. Extra precaution is
recommended on initial energization of the
equipment.
Hazardous
V o l t a g e .
Improperly installed, or
damaged equipment will
result in severe injury,
death, and property loss.
Correct all problems prior
t o
e n e r g i z i n g
t h i s
equipment.
Only qualified personnel
should
energize
this
equipment.
In order to minimize the risk of injury or
damage, there should be no load on the
controller or group
o f c o n t r o l l e r s w h e n
incoming
power
is first turned on.
All
downstream loads, including those such as
distribution
equipment
and
other
remote
devices, should be turned off. The isolation
switch ahead of each controller should be in
Fig. 48 Release Lever Engaged
Fig. 49 Preparing For Initial Energization