GENERAL DESCRIPTION
Page 25
CONTROLLER RATINGS
TABLE 2. SHORT-CIRCUIT & WITHSTAND CAPABILITY
Interrupting
Capacity
Amperes)
50,000 RMS
Interrupting
Capacity
MVA)
Short Time
Capability
30
Seconds
2 4 0 0 A
TABLE 3. CONTINUOUS CURRENT
Short Time
Capability
1 Second
6 0 0 0 A
Dielectric
Withstand
1 Minute
AC 19
DC 26
Impulse
Voltage
Withstand
BIL
6 0
Enclosure Type
Max.
Continuous
Amperes
Max.
Continuous
Amperes
One-High Controller or
Upper Controller in a
Lower Controller in a
High Stacking
High Stacking
Arrangement
Arrangement
NEMA-1
Ventilated
I
3 6 0
I
3 2 0
NEMA-1 Non-Ventilated
I
3 6 0
I
2 8 0
NEMA-12, 3R
3 1 0
2 8 0
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]