143
11
Replacement of the service PC board
Setting the jumper wires and DIP switches
Model switching (J800 to J803)
Since this service PC board is available for several models, cut the jumper wires according to the following table.
If they are not cut correctly, an error code “L10” or “L29” appears on the remote controller and the operation of the
air conditioner is disabled.
Outdoor unit
Service Parts (CDB)
HWS-P804HR-E1, P1104HR-E1
302-6V-045 (MCC-1571)
Parts name
Function
Setting
Jumper wire
J800~J803
Model switching
Cut these jumper wires according to the following table.
J804~J811
Settings
Set these jumper wires to the settings of the PC board
before replacement.
DIP switch
SW802
Settings
Set SW802 to the setting of the PC board before
replacement.
SW803
LED indication switching
Set SW803 to all OFF.
SW804
Special operations for
service
Set SW804 to all OFF.
SW805 (Only H8series)
Special operations for
service
Set SW805 to all OFF
Model name
J 800
J 801
J 802
J 803
Factory default
HWS-804H-E1
HWS-1104H-E1
HWS-1404H-E1
HWS-P804HR-E1
HWS-P1104HR-E1
* : Characters that indicate the following:
No character -- Standard models
R ----- For with cord heater
:Connected,
:Cut
<HWS-P804HR-E1, P1104HR-E1>
SW802
SW804
J800-J803
SW803
MCC-1571
AMP Air Conditioning
www.ampair.co.uk | [email protected]