121
52
External input contact logic (must be used in with
FC61)
0000: CLOSE to stop system *2
0001: OPEN to stop system *2
0002: OPEN to stop system, CLOSE to restart
system (Statics input)
0003: CLOSE to stop system, CLOSE again to restart
system (plus input)
0000:CLOSE to stop
54
Logic of 3-way valve’s action when powered (Single
return only)
0000: Not reversed (Hot water mode when powered)
0001: Reversed (Heating when powered)
0000: Not reversed
(Hot water mode when
powered)
58
Night set back is activated
0000: Zone 1 & 2
0001: Zone 1 only
0000: Zone1 & 2
59
Interval of Mixing Valve control
0001: 1 minute
-
0030: 30 minutes
0004: 4 minutes
5A
P1 setting while in hot water supply mode
0000: While running HP only
0001: P1 continues running
0000: While running
HP only
5B
Boiler running setting
0000: Boiler and HP
0001: Boiler only with pump running
0002: Heater
0003: Boiler only (Pump stopping)
0003: Boiler only
61
Changing the target of stopping/starting by external
signal or changing the TEMPO setting
0000: Hot water supply and heating
0001: Keeping initial status *3
0002: Hot water supply only
0003: Heating only
0004: TEMPO1 (Not activate the heaters)
0005: TEMPO2 (Not activate the heaters, inlet pump,
heat pump)
0000: Hot water
supply and heating
62
Activate/deactivate A02 error detection
0000: Activate
0001: Deactivate
0000: Activate
64
Continuously run or stop the P2 pump while cooling
0000: Continuously run P2
0001: Stop P2
0000: Continuous
running
65
P1 pump setting when the thermostat is deactivated in
the room temperature remote controller and room
temperature thermostat settings
0000: Continuously run P1
0001: Stop P1 when the thermostat is OFF
0000: Continuous
running
67
Changing the condition of optional output (For the
optional PC board connected to CN209)
0000: 1-3 During defrosting
2-3 While compressor is running.
0001: 1-3 As error is detected
2-3 During operation
0000: 1-3 During
defrosting
2-3 While compressor
is running.
6E
To diff temperature, when pump P1 stop at to 20 °C
0001: 1K
0005: 5K
0002: 2K
73
Hot water tank heater start time of heat-pump while
operating
0000: 30 min passed
0003: 120 min passed
0000: 30 min passed
92
Upper room temperature limit when cooling
0000: 0 °C
-
0055: 55 °C
0029: 29 °C
93
Lower room temperature limit when cooling
0000: 0 °C
-
0055: 55 °C
0018: 18 °C
94
Upper room temperature limit when heating
0000: 0 °C
-
0055: 55 °C
0029: 29 °C
95
Lower room temperature limit when heating
0000: 0 °C
-
0055: 55 °C
0018: 18 °C
96
Initial water temperature setting when controlling
cooling by the room temperature remote controller and
room temperature thermostat
0005: 5 °C
-
0030: 30 °C
0020: 20 °C
9D
Initial water temperature setting when controlling
heating by the room temperature remote controller and
room temperature thermostat
0020: 20 °C
-
0060: 60 °C
0040: 40 °C
9E
TO temperature setting to stop the P1 pump during the
middle period heating
0010: 10 °C
-
0030: 30 °C
0020: 20 °C
A0
P1 pump speed control changes the percentage duty of
the PWM control
0000: 100%
0005: 50%
0000: 100%
A1
Outside air temperature T0 temperature
-0030: -30 °C
-
-0020: -20 °C
-0020: -20 °C
A2
Zone2 temperature setting method
0000: Percentage (FC31)
0001: Fixed value (FCA3~ A5)
0000: Percentage
A3
Set temperature A' with outside temperature of T0
0020: 20 °C
-
0060: 60 °C
0040: 40 °C
A4
Set temperature B' with outside temperature of T1
0020: 20 °C
-
0060: 60 °C
0035: 35 °C
FC
Item
Details
Factory default
*1 FC_01 is needed for PCB replacement or function code reset procedure has been completed.
*2 System restart with remote controller.
*3 Restart in the mode when stopping.
*4 In addition, it is enable only when switch 2-3 is set to “OFF” and FC61 is set to “3”.