117
6
Suction temperature (TS) sensor
Heat exchange temperature
(TE) sensor
Outdoor temperature (TO)
sensor
Remove the connector and measure the resistance value with a tester.
10-20 k
Ω
(Normal temperature)
7
Discharge temperature (TD)
sensor
Remove the connector and measure the resistance value with a tester.
No.
Component name
Check procedure
Temperature
0 °C
10 °C
20 °C
30 °C
Sensor (k
Ω
)
Outdoor heat exchange temperature sensor (TE)
33.8
20.4
12.6
8.0
Suction temperature sensor (TS)
Temperature
0 °C
10 °C
20 °C
30 °C
Sensor (k
Ω
)
Discharge temperature sensor (TD)
161.3
99.0
62.4
40.2
AMP Air Conditioning