10. Hot Water Boost Setting
This setting heats the water whenever necessary by using the heat pump and hot water cylinder heater.
1
Press the HOT WATER
button to start a hot water
supply operation.
(Normal hot water supply operation)
2
Pressing the HOT WATER BOOST
button displays the
symbol. (See display
)
(The set temperature does not change) The hot water supply operation
of 75 °C starts.
HOT WATER BOOST operation with the heat pump and heater ends when
the water temperature reaches 75 °C; however, the normal hot water
supply operation automatically starts after 60 minutes even if the
temperature is not as high as 75 °C.
3
Pressing the HOT WATER BOOST
button again makes
disappear, and the HOT WATER BOOST ends.
<How to set HOT WATER BOOST operation time and temperature>
In FC_08 or 09 (See 10-2-2 (See page 119)), the operation time and set temperature can be changed.
FC_08: Operation time change range 30 to 120 minutes (60 minutes: default)
FC_09: Set temperature change range 40 to 80 °C (75 °C: default)
11. Night time Low-noise Setting
• This setting is used to reduce noise output, from the outdoor unit, during
night time for neighbours. Night time low-noise operates with lower
operation frequency and fan tap than usual only for the set time period.
• The operation is the same as usual hot water supply, heating, or cooling.
• Adjust the unit time before making the settings.
<How to enable, set start time and end time of night time low-
noise>
1
Press the TEST
and TEMP.
button at the same
time for 4 seconds or longer. (See display
)
(Moves to the night time low-noise setting mode)
"09" displayed in the Code No. field and the DATA currently
displayed,
, and
blink.
2
Press TIME
to set enabled "1" or disabled "0".
Pressing SET
changes DATA and
indication to be lit and the setting is confirmed. (For DATA, only
1 or 0 can be selected.)
3
Press the TEMP.
button to change Code No. to "0A". DATA and
indication again
blink.
4
Press the TIME
button to set start time. Pressing SET
changes DATA and
indication to be lit and the setting is confirmed.
5
Press the TEMP.
button to change Code No. to "0B". DATA and
indication again
blink.
6
Press the TIME
button to set end time. Pressing SET
changes DATA and
indication to be lit and the setting is confirmed.
7
Press TEST
to exit the night time low-noise time setting mode.
and
indications go
out.
2,3 1
2,
4,
6
3,
5
1
4,6
7