H9 ASD Installation and Operation Manual
119
RX2 (AI1) Input Point 2 Rate
Program
⇒
Torque
⇒
Setpoints
This parameter is used to set the gain and bias of the RX2 (AI1) input terminal
when the RX2 (AI1) terminal is used as the control input while operating in the
Torque Control mode.
Torque Control is accomplished by establishing an associated V/f output
pattern for a given RX2 (AI1) input level.
This parameter sets RX2 (AI1) Input Point 2 Rate and is the output torque
value that is associated with the setting of RX2 (AI1) Input Point 2 Setting
when operating in the Torque Control mode.
This value is entered as -250% to +250% of the rated torque.
See RX2 (AI1) Input Point 1 Rate for more information on this setting.
Direct Access Number — F227
Parameter Type — Numerical
Factory Default — 100.00
Changeable During Run — Yes
Minimum — -250.00
Maximum — +250.00
Units — %
F227
F227