6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 826 -
to be treated as PLC#1 and PLC#2 in Table 4.9-3. Note that the user should set
PLC
for scheme
switch [
TPOS01-LGP2EXOT
].
TPOS01 function (Function ID: 513001)
Assign to BOs
Operate Cmd.
with ILK
† condition
S
R
0.1
– 50.0 s
[
TPOS01-CPW
]
Operate Cmd.
without ILK
† condition
Operate condition
‡
[
TPOS01-LGCTRCON
]
Fixedlogic
Fixedlogic
[
TPOS01-LGP2EXOT
]
Command
“PLC-P2-Control” requiring ILK check
(PLC#3 connection point)
ILK
†
condition (“P2”) passed
TPOS1-P2
TPOS01IN_TMP_28
513001 810401EE57
User configurable condition
(PLC#3 connection point)
“TPOS01_P2EC_OK_CSF”
(513001 8004011E7F)
&
&
1
≥
&
1
≥
1
≥
&
&
&
“TPOS01_P2EX_BO”
(513001 8204011DD3)
§§
Input
Output
Operate logic in TPOS01
To BO connection
“TPOS01_P2EC_OK_CS”
(513001 8304011E82)
[
TPOS01-PLSM
]
*
Fix
Var
Operation Failed
[
TPOS01-RST
]
ASEQ function
§
” is in progress
ASEQ_MULTI_SEL
“TPOS01_P2EC_OK_CSF”
(513001 8004011E7F)
“TPOS01_EX_FFL”
(513001 8604011E91
‡‡
To
“Wait for a command”
&
Detection of state-change in a device
&
TPOS01IN_TMP_38
513001 820401EE5E
User configurable condition
(PLC#2 connection point)
1
≥
&
“TPOS01_EX_CMP”
(5130018004011E93)
Operation Completed
1.0s- 100.0s
0
t
DEV01_P2_INTERLOCK
513001 800401EE33
Command
“PLC-P2-Control” not requiring ILK check
(PLC#4 connection point)
DEV01_P2_COMMAND
513001 800401EE32
Figure 4.9-41 Operate P2-Control by the PLC function in TPOS01
††
†Note: The ILK function can provide the criteria foe operation for “P2” control.
‡Note: An “operate condition” signal is generated in the operate-condition logic (Figure
Fixlogic
is set for scheme switch [
TPOS01-LGCTRCON
]. If an
alternative “operate-condition programmed by the user is required in place of the
signal generated by the original operate-condition logic, connect the alternative
“operate-condition” to the logic shown in Figure 4.9-41 using connection point #3
“User configurable condition” That is, set the scheme switch [
TPOS01-
LGCTRCON
] to
PLC
and use “TPOS01IN_TMP_28”.
§Note: The ASEQ function can provide sequential signals for automatic control.
*Note: The user can set the type of output signal. When
Var
is set for the scheme switch
[
TPOS01-PLSM
], the output period of the signal is defined by the setting applied
to [
TPOS01-CPW
]. When
Fix
is set, the signal ceases when the 43S or an ES is
changed.
‡‡Note: The “Operate failed” signal is issued when the state-change is not detected until
after reaching the time set by the setting [
TPOS01-RST
]
§§Note: The signal “TPOS01-PIEX-BO” is issued when
Fixlogic
is set for [
TPOS01-
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......