TOSHIBA
6F3H1048
1 1 .3.4
Complete Shutdown
This section shows the procedure to turn off the control power and shut down the UPS
completely.
Table 1 1 .4 Complete Shutdown
Step
Procedu re
LCD/LE D Status
1 -3
Same as steps 1 -3 in Section 1 1 .3.3 "Stop."
4
Scroll the LCD screen
to see the DC I N PUT
and make sure DC bus
voltage is OV.
5
(see 1 0.2.4 "LCD
Scroll" on page 36)
Turn off the control
power supply switch
(8A) *
DC INPUT
DC-V
O[V]
BATT-V O[V]
BATT- I
O[A]
Nothing is displayed on the LCD and all LEOs are off.
6
Turn off all breakers at
( Shutdown is completed and U PS is isolated .)
AC output, Bypass
*
I nput & AC Output.
This operation is different from the displayed instruction on the screen .
B e sure t o perform the procedure specified here.
- 40 -