3.
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
!
his in�truction contains im�ortant
Instructions for GBOOOU Senes 1 50,
225 and 300kVA that should be followed during the installation, operation, and maintenance of the U PS
systems. Please refer to the battery manufacturer's instructions for details on operating and
maintaining the batteries for each system .
U PS System's input and output are NOT equipped with a n over-cu rrent protection device, nor a n output
disconnection at the AC output. Therefore, a circuit breaker should be provided by the user between the
U PS output and the critical load input. The minimum device ratings should be as follows:
Model
1 50kVA
300kVA
Rated Output
4BOV/277Vac
4BOV/277Vac
Breaker Rating
4BOV-225A
4BOV-500A
Model
225kVA
Rated Output
4BOV/277Vac
Breaker Rating
4BOV-350A
Circuit breakers should be provided by the user between AC input (or Bypass input) and power sources.
The minimum device ratings should be as follows:
Model
1 50kVA
300kVA
Rated I nput
4BOV/277Vac
4BOV/277Vac
Breaker Rating
4BOV-225A
4BOV-500A
Model
225kVA
Rated I nput
4BOV/277Vac
Breaker Rating
4BOV-350A
The maximum ambient temperatures in which the U PS should be operated is 40°C (1 04°F) , and 32°C
(gO°F) maximum if the battery system is subject to the same ambient temperature.
The nominal battery voltage for these models is 360Vdc. The nominal battery float voltage is 405Vdc.
Only a certified service representative with battery experience should perform service on batteries. Keep
unauthorized people away from batteries.
Please refer to the battery manufacturer's instruction when battery maintenance and/or replacement are
scheduled.
LL
CAUTION
Misuse of this equipment could result in personal injury and/or
equipment damage.
In no event will Toshiba Corporation be responsible or liable for either
indirect or consequential damage or injury that may come from the use
of this equipment.