125
9-6-2. Outdoor unit
No.
Component name
Check procedure
1
Compressor
Type
DA220A2F-22L
(803H-E)
DA422A3F-25M
(1103,1403H-E)
DA422A3F-27M
(1103, 1403, 1603H8(R)-E)
Measure the resistance value of each winding with a tester.
2
Outdoor fan motor
Type
ICF-280-A60-1
(803H-E)
ICF-280-A100-1
(1103,1403H-E)
(1103 to 1603H8(R)-E)
Measure the resistance value of each winding with a tester.
3
4-way valve coil
Type
VHV-01AP552B1
STF-01AJ 502E1
Measure the resistance value.
803 to 1403H-E
1473
Ω
± 103
Ω
1103 to 1603H8(R)-E
1435
Ω
± 144
Ω
4
Pulse motor valve coil
Type
CAM-MD12TF-15
(802H-E)
Measure the resistance value.
Type
UKV-A025 0100
(1103,1403H-E)
(1103 to 1603H8(R)-E)
Red
White
Black
803 to 1403H-E
Location
Resistance
value
Red
−
White
1.04-1.16
Ω
White
−
Black
1.04-1.16
Ω
Black
−
Red
1.04-1.16
Ω
At 20°C
1103 to 1603H8(R)-E
Location
Resistance
value
Red
−
White
0.75-0.83
Ω
White
−
Black
0.75-0.83
Ω
Black
−
Red
0.75-0.83
Ω
At 20°C
Red
White
Black
Location
Resistance value
802H-E
Red
−
White
32.6 ± 3.3
Ω
White
−
Black
Black
−
Red
1103,1403H-E
1103 to
1603H8(R)-E
Red
−
White
14.8 ± 1.5
Ω
White
−
Black
Black
−
Red
1 White
6 Red
3 Orange
Yellow
2
Blue
4
M
Location
Resistance
value
Red
−
White, Orange
42-50
Ω
Red
−
Yellow, Blue
42-50
Ω
Condition 20°C
M
1 Black
6 Grey
3 Red
Yellow
2
Grey
6
Orange
4
Location
Resistance
value
Grey
−
Black, Red
43-49
Ω
Grey
−
Yellow, Orange
43-49
Ω
Condition 20°C