120
[F08]
<Indication 1> <Indication 2>
[Outside air temperature sensor (TO) failure]
[F12]
<Indication 1> <Indication 2>
[Suction temperature sensor (TS) failure]
[F13]
<Indication 1> <Indication 2>
[Heat sink temperature sensor (TH) failure]
[F15]
<Indication 1> <Indication 2>
[Heat exchanger sensor (TE, TS) wrong wiring]
Check code
Outdoor LED
indication
Check and Action procedure
(No specific description indicates outdoor unit parts.)
TO sensor connector (CN602)
is connected
Correct TO sensor
connection
Replace outdoor control board
No
Yes
TO sensor resistance
characteristic is normal
Replace TO sensor
No
See the
characteristic table
on page 101
Yes
PC-Board
803 to 1403H-E (MCC-1571)
1103 to 1603H8(R)-E (MCC 1599)
TS sensor connector
(CN600) is connected
Correct TS sensor
connection
Replace outdoor control board
No
Yes
TS sensor resistance
characteristic is normal
Replace TS sensor
No
Yes
PC-Board
803 to 1403H-E (MCC-1571)
1103 to 1603H8(R)-E (MCC 1599)
Replace outdoor control board
PC-Board
803 to 1403H-E (MCC-1571)
1103 to 1603H8(R)-E (MCC 1599)
TE and TS sensor is
attached to the correct position.
Correct sensor attaching
position
Replace outdoor control board
No
Yes
TE sensor resistance
characteristic is normal
Replace TE sensor
No
See the
characteristic table
on page 101
See the
characteristic table
on page 101
Yes
TS sensor resistance
characteristic is normal
Replace TS sensor
No
Yes
PC-Board
803 to 1403H-E (MCC-1571)
1103 to 1603H8(R)-E (MCC 1599)