5.OUTDOOR UNIT
Engineering Data book
44
5
5-1. Specification
Outdoor unit
HWS-802H-E
HWS-1102H-E
HWS-1402H-E
Power supply
1 ~ 230V 50Hz
Compressor
Type
Hermetic compressor
Motor
kW
2.0
3.75
3.75
Pole
4
4
4
Refrigerant charged
1.8
2.7
2.7
Refrigerant control
Pulse motor valve
Pipe length
Minimum
m
5
3
Standard
m
7.5
7.5
Maximum
m
30
Height difference
Outdoor-Hydro unit
m
30
Appearance
Color
Silky shade (Muncel 1Y8.5-0.5)
Material
Pre-coated material
Outer dimension
Height
mm
890
1340
Width
mm
900
900
Depth
mm
320
320
Unit weight
kg
63
93
Packing dimension
Height
mm
975
1425
Width
mm
971
971
Depth
mm
436
436
Total weight
unit and packing
kg
69
100
Heat exchanger
Type
Finned tube
Fan unit
Fan
Propeller fan
Standard air flow
m
3
/min
57
101
103
Motor
W
63
100+100
100+100
Sound pressure level
Heating nomal
dBA
49
49
51
Heating low noise*
dBA
42
44
44
Cooling normal
dBA
47
50
51
Cooling low noise*
dBA
44
45
45
Hot water normal
dBA
49
49
51
Hot water low noise
dBA
42
44
44
Operation outdoor temp
Heating
°C
-20 to 25
Cooling
°C
10 to 43
Hot water
°C
-20 to 43
Refrigerant pipe
Gas
mm
15.9
Liquid
mm
9.5
Maximum running current
A
20.8
22.8
Installation fuse rating
A
25
(all types can be used)
Power wire
H07 RN-F or 60245 IEC 66
(2.5 mm
2
or more)
Hydro/outdoor connecting wires
H07 RN-F or 60245 IEC 66
(1.5 mm
2
or more)
Содержание ESTIA HWS-1102H-E
Страница 3: ...2 1 INTRODUCTION ...
Страница 7: ...6 2 SYSTEM OVERVIEW ...
Страница 10: ...9 3 SYSTEM SPECIFICATION ...
Страница 12: ...11 4 HYDRO UNIT ...
Страница 44: ...43 5 OUTDOOR UNIT ...
Страница 57: ...56 6 HOT WATER CYLINDER ...
Страница 63: ...62 7 HYDRO UNIT INSTALLATION MANUAL ...
Страница 107: ...105 8 OUTDOOR UNIT INSTALLATION MANUAL ...
Страница 108: ...AIR TO WATER HEAT PUMP Outdoor Unit Model name HWS 802H E HWS 1102H E HWS 1402H E Installation manual ...
Страница 131: ...129 9 OWNER S MANUAL ...
Страница 146: ...Air to Water Heat Pump Engineering Data Book Aug 2009 ...