E6581737
- 30 -
3.4.6.8.
fd03
(Output current (real time))
The output current is read into 0.01% of units and by the hexadecimal number.
For example, when the output current of the rated current 4.8A drive is 50% (2.4A), 0x1388 (hexadecimal
number) is read out.
Since the minimum unit is 0.01%,
0x1388 (Hex.) = 5000 (Dec.) * 0.01 = 50 (%)
Also about the following parameters, these are the same as this.
-
fd05
(Output voltage (real time)) .............................................Unit: 0.01% (V)
-
fd04
(Voltage at DC bus (real time)) .......................................Unit: 0.01% (V)
-
fd18
(Torque) ..........................................................................Unit: 0.01% (Nm)*
* When the motor information connected to the drive set to the parameter (
f405
-
f415
), torque monitor
value "100%" is same as the rated torque of a motor in general.
3.4.6.9.
fe35
,
fe36
,
fe37
(Monitoring of the analog input VIA, VIB, VIC)
VIA terminal board monitor: "Communication Number
fe35
"
VIB terminal board monitor: "Communication Number
fe36
"
VIC terminal board monitor: "Communication Number
fe37
"
These monitors can also be used as A/D converters irrespective of the drive's control.
VIA / VIC terminal board monitor is capable of reading the data from external devices in a range of 0.01 to
100.00% (unsigned data: 0x0000 to 0x2710).
VIB terminal board monitor is capable of reading the data from external devices in a range of -100.00 to
100.00% (signed data: 0xD8F0 to 0x2710).
If analog input mode is selected with the frequency setting mode selection parameter, however, keep in mid that
any data entered via an analog terminal is regarded as a frequency command.
3.4.6.10.
fe14
(Cumulative run time)
The operated cumulative time is read by the hexadecimal number.
For example, when cumulative operation time is 18 hours, 0x12 (18 hours) is read.
0x12 (Hex.) = 18 (Dec., hour)
3.4.6.11.
fe40
(Analog output (FM))
The output value of FM terminal is read.
The value range is set to 0 to 10000 (0x2710).