5.2 Controller Interface
Unified Controller nv series type1 light Communication Interface Module (CF622) Instruction Manual
51
■
Send Processing Operation
----Normal mode (operation mode: mode1 - 3), CF611 mode
Trans data
(3)
TX_RDY
(6)
(2)
(4)
TX_CMP
TX_ERR
CF622 Control
User's application
MWRITE instruction
(1)
TX_ST
(5)
Send data
Send data
Figure 5-24 Send processing operation
(1) Write send data to send data area using MWRITE instruction. After the data writing is completed, set
TX_ST to 1 from user’s application.
(2) TX_RDY is set to 0 from user’s application.
(3) CF622 starts data sending.
(4) If data sending is completed, TX_CMP is set to 1.
(5) Reset TX_ST to 0 from user’s application.
(6) TX_CMP is reset to 0 and TX_RDY is reset to 1.