7-2. Operation Data
<Cooling>
Tempeature
Model name
Standard
Heat exchanger
Indoor
Outdoor
Compressor
condition(°C)
RAS-
pressure
pipe temp.
fan mode
fan mode
revolution
Indoor
Outdoor
P Psia (MPa)
T1 °F (°C)
T2 °F (°C)
(rps)
80/67 98/75 137 to 160 54 to 57 99 to 102
(26.7/19.4) (35/23.9) (0.9 to 1.1) (12 to 14) (37 to 39)
116 to 145
52 to 55
104 to 107
(0.8 to 1.0)
(11 to 13)
(42 to 44)
12EKCV-UL High High 77
High High 60
09EKCV-UL
FILE NO. SVM-13071
– 2
3
–
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchaner path U bent.
(Thermistor themometer)
2. Connecting piping condition : 16 ft (5m)