37
1600XPi Series UPS Installation and Operation Manual – 60616-014
15.2 Audible Alarm Functions
An audible alarm (buzzer) will sound when the UPS is in the battery
backup mode, has a fault, has low battery voltage, or is
in an overload condition. The buzzer will also beep each time an effective item is touched on the touchscreen. The following
chart shows the buzzer pattern durations for each condition. Time units are shown in seconds.
AUDIBLE ALARMS
Condition
Audible Pattern
Any Fault (Interrmittant buzz until fault clears)
0.5 s
0.5 s
Switch to Backup (Single five-second buzz)
5.0 s
Backup Operation (Intermittant buzz once every
ten seconds)
9.0 s
1.0 s
UPS Battery Shutdown Voltage
(Batt. Voltage 79%)
5.0 s
Warnings:
OL110 (Overload Timer)
LB (Low Battery – Batt. Voltage 90%)
BLFN (Battery Life Pre-alarm – Batt exp in 6 mo.)
BLFE (Battery Life End)
CHRGOV (Charger Over Voltage)
BTSTFL (Battery Test Fail)
BOH (Battery Overheat)
AOH (Ambient Overheat)
CLMT (Current Limit)
DCER (Display Disconnected)
BDEPL (Battery Depletion)
1.0 s
1.0 s
Touching Effective Item on Touchscreen
0.1 s
The buzzer can be silenced by selecting the Settings tab, then set the Mute Enable parameter to 1. This will turn off the
buzzer for the current alarm status, but the buzzer will still sound when the next Fault/Warning condition occurs.
The buzzer can be disabled by selecting the Settings tab then setting the Mbuzzer parameter to 0. This will disable the
alarm so that no alarm sounds for any Fault or Warning condition.
Содержание 1600XPi SERIES
Страница 2: ......
Страница 6: ...This Page Left Intentionally Blank ...
Страница 10: ...This Page Left Intentionally Blank ...
Страница 78: ...This Page Left Intentionally Blank ...
Страница 88: ...This Page Left Intentionally Blank ...
Страница 118: ...This Page Left Intentionally Blank ...
Страница 120: ...C2 1600XPi Series UPS Installation and Operation Manual 60616 014 5 2 6 kVA Dimensions ...
Страница 121: ...C3 1600XPi Series UPS Installation and Operation Manual 60616 014 8 10 kVA Dimensions ...
Страница 122: ...C4 1600XPi Series UPS Installation and Operation Manual 60616 014 14 22 kVA Dimensions ...
Страница 130: ......
Страница 132: ...E2 1600XPi Series UPS Installation and Operation Manual 60616 014 FIGURE E 2 8 22KVA BATTERY CABINET OUTLINE ...
Страница 138: ...This Page Left Intentionally Blank ...
Страница 139: ......