1600XPi Series UPS Installation and Operation Manual – 60616-014
9.7 Battery Recharging
The illustration below shows a graphical representation of the UPS battery recharge process after a full discharge.
BATTERY
CHARGE
VOLTAGE
CURRENT VOLTAGE
CHARGING
CURRENT
I
CHARGE
V
MAX
V
MIN
DISCHARGE
SHUT-OFF
POINT
PERIOD 1
PERIOD 2
PERIOD 3
TIME
FULLY
CHARGED
0
0
The recharge process usually consists of three periods. During the first period, the current is maintained at approximately 1
ampere. This current limit is the maximum value that can be used to charge the batteries (for minimal recharge time) while
assuring safety and long battery life. In the second period, constant-voltage control starts and current gradually decreases
as the batteries charge to their normal fully charged state. In the third period, a slight trickle current continues to flow into
the batteries to keep them fully charged and floating at the normal Vdc level. A full recharge usually requires 24 hours (90%
recharge in 12 hours) after a complete discharge.
The following chart shows the rated maximum and minimum battery voltages and the charge current for each of the sizes.
RATED BATTERY VOLTAGES
Model
Vmax
Vmin
Icharge
(Typical)
3.6 kVA
163 V
114 V
1.0 A
5.2–6 kVA
245.7 V
170 V
1.0 A
8 kVA
327 V
227 V
1.0 A
10 kVA
327 V
227 V
1.0 A
14 kVA
327 V
227 V
1.0 A
18 kVA
327 V
227 V
1.0 A
22 kVA
327 V
227 V
1.0 A
Содержание 1600XPi SERIES
Страница 2: ......
Страница 6: ...This Page Left Intentionally Blank ...
Страница 10: ...This Page Left Intentionally Blank ...
Страница 78: ...This Page Left Intentionally Blank ...
Страница 88: ...This Page Left Intentionally Blank ...
Страница 118: ...This Page Left Intentionally Blank ...
Страница 120: ...C2 1600XPi Series UPS Installation and Operation Manual 60616 014 5 2 6 kVA Dimensions ...
Страница 121: ...C3 1600XPi Series UPS Installation and Operation Manual 60616 014 8 10 kVA Dimensions ...
Страница 122: ...C4 1600XPi Series UPS Installation and Operation Manual 60616 014 14 22 kVA Dimensions ...
Страница 130: ......
Страница 132: ...E2 1600XPi Series UPS Installation and Operation Manual 60616 014 FIGURE E 2 8 22KVA BATTERY CABINET OUTLINE ...
Страница 138: ...This Page Left Intentionally Blank ...
Страница 139: ......