USER’S MANUAL

MAGMETER

T-500

Содержание T-500

Страница 1: ...USER S MANUAL MAGMETER T 500...

Страница 2: ...UNCTIONAL OUTPUTS B1st PULSE SETTING B2nd STATUS REPORT SETTING B3rd EXAMPLES OF STATUS REPORTS C ANALOGUE OUTPUT D DISPLAY UNITS DECIMAL PLACES E DAMPING OF SUDDEN CHANGES OF FLOW F DEAD BAND SETTING...

Страница 3: ...outputs and the third one as an active current output The stan dard delivery includes also an internal datalogger and RS232 communication port A GSM module for remote data reading via SMS text message...

Страница 4: ...range 0 1 to 0 5 m s Ambient temperature 20 to 60 C Voltage 230V AC optionally 15 24V AC 12 34V DC Input power 10 VA max Outputs 1 x programmable multifunctional pulse status isolated relay load 125 V...

Страница 5: ...GMETER T500 ED2 DN L mm Weight Kg 15 150 2 20 150 2 25 150 2 5 32 150 3 5 40 150 5 50 200 6 65 200 9 80 200 11 100 250 13 5 125 250 20 150 300 25 200 350 35 250 400 41 300 500 55 350 500 65 400 600 11...

Страница 6: ...not be in uenced by any disturbing elements as valves pumps bends or sharp deviations in the tubing section Therefore observe the following instructions when installing the ow meter into the tubing If...

Страница 7: ...interference especially for detached versions when shielding of the link cable between sensor and electronic unit is connected to the frame Remove upper cover of the instrument to get access to termi...

Страница 8: ...onal output BIN2 programmable multifunctional output ANAL programmable analogue output FREQ frequency output for calibration only 230 V L phase conductor 230 V 50 Hz 230 V PE protective conductor 230...

Страница 9: ...ANAL All outputs are isolated 2 Connect the ow sensor link cable to ABCDE terminals Not applicable for compact version where the sensor was connected in factory Terminal blocks on the sensor and on t...

Страница 10: ...particular time Besides these data it can show one of following optional values see Chapter 8 G Immediate ow rate Q Maximum ow rate reached during particular period MAX Minimum ow rate reached during...

Страница 11: ...Configuration of analogue output PULSE OUTPUTS Configuration of multifunctional pulse outputs COMPARATOR Selection of logical functions for multifunctional pulse outputs FREQUENCY OUT Configuration o...

Страница 12: ...s are used only for optotransistor Use jumper NC OC NO above BIN1 terminals to set their function a Output works as optotransistor b Relay contacts are normally open c Relay contacts are normally clos...

Страница 13: ...for both directions and con rm by EXE key Select option RETURN to nish setting 5 The instrument will ask if you want to save new parameters SAVE SETUP Select YES if they are OK The ow meter will save...

Страница 14: ...EXE key to enable editing of ow rate value co 5 rresponding to current value 20 mA Use cursor keys to set ow rate value in l s and con rm by EXE key Select option RETURN to nish setting 6 The instrume...

Страница 15: ...s the instrument responds to immediate drop of ow and displays zero ow rate only after 5 seconds Select option MODE and con rm by EXE key Select LINEAR if damping is to be linear or AVERAGE if it 4 sh...

Страница 16: ...splay mode and works with new parameters until it is switched off When the instrument is switched on again it works with original parameters Internal datalogger enables recording of measured values in...

Страница 17: ...rked with asterisk Use command RETURN to return to submenu Select option PER and con rm your selection by EXE key Use command EDIT to enable interval editing 5 in minutes Enter interval length and use...

Страница 18: ...er interval length and use command RETURN to return to submenu Select START Option RUN should be marked with asterisk this means that datalogger is operating 6 Select option RETURN to nish setting 7 T...

Страница 19: ...factory and need not to be set in most cases b If the measuring tube section is empty or incompletely ooded i e the electrode is not in contact with liquid measurement is not locked and this situatio...

Страница 20: ...the instrument displays message POWER ON and then GSM INIT 1 indicating that the instrument recognized the internal GSM module After that starting procedure is perfor med with standard messages from...