Notes:
1.
The AVR ELITE unit needs to be switched
ON at all times for series mode surge protection to be
active
.
If the AVR ELITE and connected components will not be used for an extended period of
time, it is recommended to disconnect the AVR ELITE unit from main power.
2.
There is a 20-second delay built into the AVR ELITE system, to prevent nuisance switching. The AVR
ELITE will take approximately 20-seconds to change relay taps to switch to the proper output
voltage setting.
3.
North American models: Torus AVR ELITE will keep the output constant within the range of
120±4V, with an input voltage of 180V to 260V. Between 170V to 180V, and between 260V and
270V, the regulation will be reduced.
4.
International models: Torus AVR ELITE will keep the output constant within the range of 240±8V,
with an input voltage of 180V to 260V. Between 170V to 180V, and between 260V and 270V, the
regulation will be reduced.
5.
The output current (Amps) displayed on the LCD is the RMS reading of the load. It does not
indicate the peak current loads.
6.
A drop in the input voltage is normal when increasing the load on the AVR ELITE. This is a result of
the impedance of the power line, a function of the distance from the electrical panel and
transformer regulation.