Model GPL+GLU limited service fire pump controllers are designed to start an electric motor driven fire pump. It can
either start the fire pump manually through the local start pushbutton or automatically through the sensing of a
pressure drop in the sprinkler system. The fire pump controller is supplied with a pressure transducer. The fire
pump can be stopped manually with the local stop pushbutton or automatically after the expiration of a field
programmable timer. In both cases, stopping is only allowed if all starting causes have disappeared.
Types of Limited Service Fire Pump Controllers
FIRE PUMP CATALOG NUMBER
MODEL No. EXAMPLE: GPL - 208 / 15 / 3 / 60
Model Prefix GPL
Voltage 208 V
HP Rating 15 HP
Phase 3
Frequency 60 Hz
Types of Automatic Transfer Switch
TRANSFER SWITCH CATALOG NUMBER
MODEL No. EXAMPLE: GPL+GLU - 480 / 20 / 3 / 60
Model Prefix GPL+GLU
Voltage 480 V
HP Rating 20 HP
Phase 3
Frequency 60 Hz
Methods of Starting/Stopping
The controllers are available as combination automatic / non-automatic with provision for manual or automatic
shutdown (an automatic shutdown is only possible after an automatic start).
METHODS OF STARTING
AUTOMATIC START
The controller will start automatically on low pressure detection by the pressure sensor when the pressure drops
below the cut-in threshold.
MANUAL START
The motor can be started by pressing the START push button, regardless of the system pressure.
REMOTE MANUAL START
The motor can be started from a remote location by momentarily closing a contact of a manual push button.
REMOTE AUTOMATIC START, DELUGE VALVE START
The motor can be started from a remote location by momentarily opening a contact connected to an automatic
device.
EMERGENCY START
The motor can be started manually by using the emergency push button. This button can be maintained in a closed
position.