- Enable/Disable the corresponding alarm/warning condition by pressing the square button.
- Alarm Bell Icon: Activates the bell when the condition occurs.
- Alarm Icon: If selected, the occurring condition will be an alarm. If unselected, it will be a simple warning.
-
RESET: Value at which the condition will go from the “ACTIVE” state to the “OCCURRED” state.
- SET: Value at which the system will activate the corresponding condition.
Details of the Debug Page
Calibration
Config > Advanced > Debug > Calibration
This table displays all calibration parameters. The “Scaled” value is the final calculated value used in the ViZiTouch.
It is calculated by multiplying the “Raw” value by the “Gain” coefficient and by adding the “Offset” value. This
information is useful when debugging the analog inputs on the IO board.