Config (Membrane button)
Config
Setup all basic configuration parameters.
The main configuration page provides a quick means of changing the most common settings. The padlock icon
indicates the current authorization level. A locked padlock indicates that only basic settings can be changed. Press
on the padlock to enter an authorization code to unlock additional settings. An unlocked padlock showing an
authorization number indicates that some settings are unlocked. Press on the padlock again when you have
concluded your operation.
Access Level 0:
-
The “Advanced” button activates the advanced configuration pages.
-
Date and Time adjustment are accessed by pressing the clock. Refer to the “Date and Time” page for more
information.
Access Level 1:
Inside the left box, the main pressure parameters can be set.
-
Adjustment of the pressure reading “Unit of measure”: PSI, kPa, bar, FoH, mH20
- Maximum pressure of system (between the Cut-Out value and 9999)
- Cut-Out adjustment (between the Cut-Out value and the Maximum Pressure value). It should be set before setting
the Cut-In
- Cut-In adjustment (between 0 and the Cut-Out value)
Inside the middle box, the parameters linked to the different tests can be set. To activate the weekly test, press the
white square at the lef
t of the weekly test frequency. When activated, the square turns green. The “Weekly Test
Frequency” is the text field just right of the activation square button. By clicking on it, a selection Pad will provide
three choices for the frequency of the periodi
c test: “Weekly Test”, “Bi-Weekly Test” and “Monthly Test”.
The next set of parameters is the periodic test schedule which consists of three editable fields. The first field is the
day of the week and the time, in hours and minutes. Simply press the appropriate button to set these values
accordingly. The next editable field located just below is the periodic test duration in minutes. The last section of the
middle box is the duration of the manual “Run Test”, labelled with the “Run Test” icon button as seen on the
membrane. Press the button to modify the value of the manual "Run Test" duration.