TOPVERT L1 Series
E-
31
Low voltage on DC-Bus
during run
(LUr) {36}
The drive detects that the DC
bus voltage has fallen below
its minimum value during run
Check whether the input power voltage is normal
Check whether the power supply capacity is
enough
Check for possible sudden load
Whether the 3-phase model is of the single-phase
power input or the phase-lacking
Check whether the Inrush limit by-pass circuit
fault
Check whether the input power was interrupted
Check whether the input side magnetic contactor is
normal
Low voltage on DC-Bus
(LU) {39}
The drive detects that the DC
bus voltage has fallen below
its minimum value
External Base Block
(bb) {40}
(one of Pr2-01~Pr2-03 =15 or
16 and act)
When the external input terminal (B.B) is active, the
drive output will be turned off.
Deactivate the external input terminal (B.B) to
operate the drive again.