TOPVERT G1/H1/P1 Series
E-11
FWD
FWD RUN/STOP command
Pr2-00/( FWD RUN/STOP)
REV
REV RUN/STOP command
Pr2-00/( REV RUN/STOP)
DCM
The reference point of digital signal inputs.
The reference of +24V control power supply.
These terminals are isolated from ACM terminal
Totally 2 DCM terminals with same
function.
[MI7]
[Multi-function digital input MI7]
Pr2-26
[MI8]
[Multi-function digital input MI8]
Pr2-27
[MI9]
[Multi-function digital input MI9]
Pr2-28
Relay contact outputs
Separate these control circuit wiring from wiring for other control terminals
R1A
Multi-Function digital output 1
Relay 1 (Relay dry contact output)
R1A-R1C :Relay 1 Normal open (a contact)
R1B-R1C :Relay 1 Normal close (b contact)
Pr2-20,Pr2-21
Resistive Load
5A(N.O.)/3A(N.C.) 240VAC
5A(N.O.)/3A(N.C.) 24VDC
Inductive Load
1.5A(N.O.)/0.5A(N.C.) 240VAC
1.5A(N.O.)/0.5A(N.C.) 24VDC
R1B
R1C
R2A
Multi-Function digital output 2
Relay 2 (Relay dry contact output)
R2A-R2C :Relay 2 Normal open (a contact)
R2B-R2C :Relay 2 Normal close (b contact)
R2B
R2C
Voltage source for digital signal and Frame Ground
(Use the shielded twisted-pair cables to prevent operating faults)
E
Connect to the shield net of shielded twisted-pair
cables (Frame Ground)
24V
Digital control voltage source.
Reference point is DCM
Max. 50mA
DCM
The reference point of digital signal inputs.
The reference of +24V control power supply.
These terminals are isolated from ACM terminal
Totally 2 DCM terminals with same
function.
Analog Inputs and outputs
(Use the shielded twisted-pair cables to prevent operating faults)
+VX
+12V/+10V selectable reference voltage source.
Reference point is ACM.
Max.20mA/(+12V)
-12V
-12V reference voltage source.
Reference point is ACM
Max. 20mA
AI1
Multi-Function analog input 1 (voltage command
or current command selectable)
(when AI1 analog input selector switch to “V” can
accept DC 0~10V voltage signal. when switch to
“I” can accept DC 4(0)~20mA current signal.
Pr3-02/
(DC 0~10V corresponding to the
maximum operation frequency)
AI2
Multi-Function analog input 2 (current command
or voltage command selectable)
(when AI2 analog input selector switch to “V” can
accept DC 0~10V voltage signal. when switch to
“I” can accept DC 4(0)~20mA current signal.
Pr3-06/(4~20mA)
AI3
Multi-Function analog input 3 (accept DC
-10~+10 0~10V voltage signal.)
Pr3-11
ACM
The reference point of analog inputs and outputs
signal.
The reference of reference voltage source.
These terminals are isolated from DCM terminals
Содержание TOPVERT E1 Series
Страница 1: ...ISO 9001 2008 High performance Vector Control AC drive TOPTEK ELECTRONICS CORPORATION QUICK START...
Страница 40: ...TOPVERT G1 H1 P1 Series E 39...
Страница 41: ...TOPVERT G1 H1 P1 Series E 40...
Страница 76: ...TOPVERT G1 H1 P1 C 35...
Страница 77: ...TOPVERT G1 H1 P1 C 36...