TOPVERT G1/H1/P1 Series
E-26
programmed step
speed when PLC
Run Paused
Bit 3
(bx0xxx)
0
Re-Execute PLC
Run from step 0
after recover from
power interruption
1
Continue Execute
PLC Run from the
point which power
interrupted after
recover from
power interruption
Pr4-34
PLC Run operation cycle
0~60000 : 0~60000 cycle
0
0= PLC Run disabled
60001: Continuously execute
recurring cycles
Pr4-35
What to do after PLC Run completed
0~15
:
step speed
(0=master speed)
16
16
:
stop
Pr4-36
Multi-Step Speed Run (MSS RUN) operation
mode
Bit 0
(bxxxx0)
0
Direction
determined by
Pr4-32
b00001
1
Direction
determined by the
master speed
Bit 1
(bxxx0x)
0
Duration of MSS
Run determined
by Mix terminals.
1
Duration of MSS
Run determined
by Pr4-15~Pr4-30
setting.
Bit 2
(bxx0xx)
0
Without zero
intervals
(Continue mode)
1
With zero
intervals (Stop
mode)
Bit 3
(bx0xxx)
0
Jog command
ineffective during
Run
1
Jog command
effective during
Run
Group 5: Motor parameters and protection parameters
Paramet
ers
Functions
Settings
Factory
Setting
User
★
Pr5-00
Full-Load Current of Motor 1
Amp (10~120% of drive’s rated current)
##.##
Pr5-01
Auto Torque Compensation of Motor 1
0.0
~
25.0%
0.0
Pr5-02
Slip Compensation of Motor 1
0
~
20 RPM
0
Pr5-03
Number of Motor Poles 1
2
~
20
4
Pr5-04
Rotor Resistance R1 of Motor 1
0.000
~
65.535
Ω
0
★
Pr5-05
Auto-tuning & control mode selection
0: No function
0
1: To execute auto-tuning and switch to
Sensorless vector control mode
2: Reset to V/F control mode
★
Pr5-06
Low Voltage Level l
230V models: 160
~
220VAC
180
460V models: 320
~
440VAC
360
◎
575V models: 400
~
550VAC
450