11
TECHNICIAN SETUP MENU
TECH SETUP
STEPS CONTINUED
ON THE NEXT PAGE
Use the or
key to select the
maximum heat
setpoint.
90 ºF
Adjustment Options
Factory Default Settings
This feature
allows you to set a
maximum heat
setpoint value.
The setpoint
temperature
cannot be raised
above this value.
Tech Setup Steps (Continued from the previous page)
Heating
Temperature
Setpoint Limit
LCD Will Show
Use the or
key to select the
minmum cool
setpoint.
44 ºF
This feature
allows you to set a
minimum cool
setpoint value.
The setpoint
temperature
cannot be lowered
below this value.
Cooling
Temperature
Setpoint Limit
Use the or
key to select 12 or 24
hour clock.
12 Hour Clock
You can select
either a
12
or
24
hour clock setting.
12 or 24
Hour Clock
Use the or
key to turn on or off.
ON
This feature turns your
system on before the
WAKE
programming
time to ensure the
enviroment is at the
WAKE
setpoint when
the
WAKE
time period
begins. This recovery
changes over time
based on the previous
day’s experience.
Morning
Recovery
Use the or
key to select
7d
for 7
day,
5d
for 5+1+1,
or
0d
for
nonprogammable.
5d
You can configure this
thermostat to have a
7 day program, a
5+1+1 program or
nonprogrammable.
Program
Options
Select
F
for
Fahrenheit
temperature read
out or select
C
for
Celsius read out
ºF for Fahrenheit
ºC for Celsius
ºF
ºF or ºC
The second stage will turn on at 2x the swing setting. The second stage will turn off when 1x the swing is
reached. For example, if the swing setting is .8 degrees for heating and the thermostat is set at 70ºF, the
first stage will turn on at approximately 69.2ºF. The second stage will turn on at 68.4ºF. The second stage
will turn off at 69.2ºF and the first will turn off at 70.8ºF. If third stage is used, it will turn on at 3x the swing
and turn off at approximately 2x the swing.
Balance Point:
The system operates differently when a balance point is used on a dual fuel system. The balance point
outdoor temperature setting will be the outdoor temperature at which the thermostat chooses either the
heat pump or gas furnace.
For Example:
A balance point setting of 30ºF will turn on only the heat pump
above 30ºF and only the gas furnace below 30ºF.
Y1
will be stage one above 30ºF and
W2
will be stage
one below 30ºF.
PRO1 Tip
OFF
configures display
light to come on only
with the light key,
which will save battery
power.
ON
configures the
display light to come
on when any key is
pressed.
ON
The display light can
be configured to come
on when any key is
pressed or only when
the light key is pressed.
Display
Light