instructions for installation
CONFIGURATION OF AUTOMATION PARAMETERS
ref.
display
parameter description
val.
*default*
value description
105
SAFETY LOGIC
Setting with logic of the 4 safety sensors. For values
0 to 3, if the safety sensor on opening is enabled, the
door will then close.
For values from 4 to 7, if the safety sensor on
opening is enabled, the door will close again only
if the sensor is not enabled in the time set with
parameter 122.
0
*1*
2
3
4
5
6
7
NO with active low test (to GND)
NC with active high test (NC with test 24V)
NO without test
NC without test
NO with low active test and pause time on obstacle equal to paraeter”122”
NC with high active test and pause time on obstacle equal to paraeter”122”
NO without test and pause time on obstacle equal to parameter”122”
NC without test and pause time on obstacle equal to parameter”122”
106
SEQUENTIAL RADAR FUNCTION
One activation radar controls door opening and
another controls closure. Only entry or only exit
functions do not work with the analogue switch.
*0*
1
2
Disabled
Enabled from inside to outside
Enabled from outside to inside
107
FIRE ALLARM INPUT LOGIC
A command on this input causes the door to open
even when it is closing. When this command is
disabled the automation returns to the previous state.
*0*
1
NO
NC
108
INPUT OPEN
A command on this input causes opening of the door
even when it is closing.
*0*
1
NO
NC
109
HARD RESET
Resets to the native state. Serves to return the
machine to the factory status. Press ENTER twice to
confirm the selection.
0
RESET
110
BATTERY.
Behavior of automation in case of
blackout on the power mains
*0*
1
2
3
4
5
No battery
Opens
Opens except when closing
Opens except when closing, exit only or entry only.
Closes
Continuous operation
111
OPEN ONLY ONE LEAF
Function used with double wing doors if only one
wing is enabled, the master wing.
*0*
1
Disabled
Enabled
112
OUTPUT ELB2 SIGNAL LED.
Selection of behavior for signal led.
*0*
1
2
3
4
5
Disabled
Signaling if “on moving”
Signaling if “on error”
Signaling if “on needing maintenance”
Signaling the status
Signaling if “a safety sensor (opening/closing) is activated”
113
SERVO Push & GO
*0*
1
2
3
Disabled
PUSH&GO: Serves for use of the Push&Go function.
SERVO with sensors disabled: Manual opening servo assisted
SERVO with sensors enabled: Manual opening servo assisted.
Содержание M200
Страница 20: ...M200 20 instructions for installation LIST OF ERROR MESSAGES AND NOTICES ...
Страница 28: ...M200 28 instructions for installation EC DECLARATION OF INCORPORATION ...
Страница 29: ...29 instructions for installation M200 ...
Страница 30: ...M200 30 instructions for installation ...
Страница 31: ...31 instructions for installation M200 ...